SIMATIC NET
Industrial Ethernet switches
SCALANCE XF-200BA
Operating Instructions
09/2018
C79000-G8976-C470-03
Introduction
Safety notices
Recommendations on
network security
Description of the device
Installation
Connecting up
Upkeep and maintenance
Technical specifications
Dimension drawings
Approvals
1
2
3
4
5
6
7
8
A

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SCALANCE XF-200BA

  • Page 1 Introduction Safety notices Recommendations on network security SIMATIC NET Description of the device Industrial Ethernet switches SCALANCE XF-200BA Installation Connecting up Operating Instructions Upkeep and maintenance Technical specifications Dimension drawings Approvals 09/2018 C79000-G8976-C470-03...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Introduction

    These operating instructions apply to the following devices: ● SCALANCE XF204-2BA ● SCALANCE XF204-2BA DNA Unless mentioned otherwise, the descriptions in these operating instructions refer to all devices of the SCALANCE XF-200BA product group named in the section on validity. Designations used Classification Description...
  • Page 4 ● On the data medium that ships with some products: – Product CD / product DVD – SIMATIC NET Manual Collection ● On the Internet pages of Siemens Industry Online Support under the following entry IDs: – Industrial Ethernet / PROFINET Industrial Ethernet System Manual (https:// support.industry.siemens.com/cs/ww/en/view/27069465)
  • Page 5 Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customers’...
  • Page 6 Introduction Catalogs You will find the article numbers for the Siemens products of relevance here in the following catalogs: ● SIMATIC NET Industrial Communication / Industrial Identification, catalog IK PI ● SIMATIC Products for Totally Integrated Automation and Micro Automation, catalog ST 70 ●...
  • Page 7: Table Of Contents

    Connecting up............................39 Safety when connecting up....................39 Industrial Ethernet........................40 5.2.1 Electrical..........................41 5.2.2 Optical............................42 Wiring rules..........................43 Power supply..........................43 Signaling contact........................45 Grounding..........................46 Upkeep and maintenance...........................47 Downloading new firmware using TFTP without WBM and CLI..........47 Restoring the factory settings....................48 SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 8 Table of contents Technical specifications..........................49 SCALANCE XF-200BA technical specifications..............49 Cable lengths.........................51 Switching properties.......................51 Mechanical stability (in operation)..................52 Dimension drawings...........................53 Approvals..............................55 Index................................63 SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 9: Safety Notices

    This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or non-hazardous locations only. This equipment is suitable for use in Class I, Zone 2, Group IIC or non-hazardous locations only. SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 10 Safety notices SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 11: Recommendations On Network Security

    Industrial Security (https://www.siemens.com/ industrialsecurity) website. ● Inform yourself regularly about security recommendations published by Siemens ProductCERT (https://www.siemens.com/cert/en/cert-security-advisories.htm). ● Only activate protocols that you require to use the device. ● Restrict access to the management of the device with rules in an access control list (ACL).
  • Page 12 ● Verify certificates and fingerprints on the server and client to prevent "man in the middle" attacks. ● It is recommended that you use certificates with a key length of at least 2048 bits. ● Change certificates and keys immediately, if there is a suspicion of compromise. SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 13 ● If you use RADIUS for management access to the device, activate secure protocols and services. Interfaces security ● Disable unused interfaces. ● Use IEEE 802.1X for interface authentication. ● Use the function "Locked Ports" to block interfaces for unknown nodes. SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 14 Default port sta‐ Configurable Authentication Encryption Port number port TELNET TCP/23 Open TCP/22 Open HTTP TCP/80 Open HTTPS TCP/443 Open ✓ SNMP UDP/161 Open ✓ Yes (when con‐ figured) PROFINET UDP/34964 Open UDP/49154 - 49157 SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 15 Protocol/ Default port sta‐ Configurable Authentication Encryption Port number port EtherNet/IP TCP/44818 Closed ✓ UDP/2222 (Open with UDP/44818 EtherNetIP var‐ iants) DHCP UDP/67 Closed ✓ UDP/68 Port number can be configured via the WBM. SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 16 Recommendations on network security SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 17: Description Of The Device

    CPU are further reduced and the availability of the entire network significantly increased. Via the SCALANCE XF204-2BA the Y switch is connected to the H-CPU. The SCALANCE XF204-2BA does not have Y functionality, it supports VLANs. SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 18 SIMATIC CFU SIMATIC CFU PROFIBUS PA Figure 3-1 Linking S2 devices into a fault-tolerant H system with SCALANCE XF-200BA Protection of the Y functionality Between the two Y ports of the SCALANCE XF204-2BA DNA there is no device-internal communication. if you change the ring ports in the configuration, the two remaining ports automatically become Y ports.
  • Page 19: Product Overview

    Factory setting Y ports SCALANCE XF204-2BA P1.1 and P2.1 SCALANCE XF204-2BA DNA P1.1 and P2.1 P1.2 and P2.2 ● Trust mode: Trust CoS ● IGMP Snooping/IGMP Querier: Off ● IPv4 Address Collision Detection: Never give up SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 20 Description of the device 3.2 Product overview Type designation The type designation of a SCALANCE XF-200BA is made up of several parts that have the following meaning: Standard version Dual Network Access Number of bus adapters Number of usable ports...
  • Page 21 Description of the device 3.2 Product overview Accessories The following accessories are available for SCALANCE XF-200BA: PLUG Component Description Article number C-PLUG Configuration plug, exchangeable storage medi‐ 6GK1 900-0AB00 um for configuration data BusAdapter Component Description Article number BA 2×RJ45 *...
  • Page 22 The strain relief is avail‐ able as an optional accessory. 5 units per pack, including screws Cable ties are not included with the product. SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 23: Spare Parts

    5 Device views The following figure shows an overview of the components of the SCALANCE XF-200BA. ① BaseUnit with slots for 2 bus adapters without covers The BaseUnit provides the electrical and mechanical connection of the bus adapters.
  • Page 24: Set Button

    EXPLOSION HAZARD Do not press the SET button if there is a potentially explosive atmosphere. Position The "SET" button is located on the front of the SCALANCE XF-200BA. Figure 3-2 Position of the "SET" button on the SCALANCE XF-200BA Resetting the device to factory defaults...
  • Page 25: Led Display

    With a redundant power supply, you can use the configuration to show which power supply is connected. No external power supply is connected. 3.5.2 "F" LED The "F" LED shows the fault/error status of the device. SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 26: Rm" Led

    An interruption has been detected on the ring and the device has switched through. C-PLUG 3.6.1 Function of the C-PLUG NOTICE Do not remove or insert a C-PLUG during operation A C-PLUG may only be removed or inserted when the device is turned off. SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 27 Inserting a C-PLUG that does not contain the configuration of a compatible device type and inadvertently removing the C-PLUG, or general malfunctions of the C-PLUG are indicated by the diagnostic mechanisms of the device. ● Fault LED ● Web Based Management (WBM) ● SNMP SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 28: Replacing The C-Plug

    Removing a C-PLUG 1. Turn off the power to the device. 2. Insert a screwdriver between the front edge of the C-PLUG (A) and the slot and release the C-PLUG. 3. Remove the C-PLUG. SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 29 1. Turn off the power to the device. 2. The housing of the C-PLUG has a protruding ridge on the long side (B). The slot has a groove at this position. Insert the C-PLUG correctly oriented into the slot. SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 30 Description of the device 3.6 C-PLUG SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 31: Installation

    The device is intended for indoor use only. WARNING The device may only be operated in an environment with pollution degree 1 or 2 (see IEC 60664-1). WARNING Substitution of components may impair suitability of the equipment. SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 32 60 °C. WARNING Wall mounting outside of the control cabinet or housing does not fulfill the requirements of the FM approval. SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 33 If you use components and accessories that are not approved for SIMATIC NET devices or their target systems, this may violate the requirements and regulations for safety and electromagnetic compatibility. Only use components approved for the SIMATIC NET devices. SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 34: Mounting On Din Rails

    2. Press the device down against the DIN rail until the spring catch locks in place 3. Fit the connectors for the power supply, see the section "Connecting up (Page 39)". 4. Insert the terminal blocks into the sockets on the device. SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 35: Mounting Bus Adapters

    ● The event is shown in the log and error table. To reactivate the bus adapter slot, restart the device: ● The bus adapter slot is active. ● The red fault LED "F" goes off. SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 36 3. If necessary mount a strain relief, see section "Mounting tensile strain relief (Page 37)". ① 4. Plug the bus adapter parallel into the BaseUnit until it can be heard to lock in place SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 37: Mounting Tensile Strain Relief

    ● Cable ties We recommend cable ties with a width of 4.8 mm. The maximum width is 7.0 mm. The length of the cable tie is min. 60 mm. Installation Figure 4-4 Mounting tensile strain relief SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 38 1. Release the cable from the strain relief and pull the cable. 2. Remove the bus adapter, see section "Mounting bus adapters (Page 35)". 3. Loosen the screw connection. 4. Remove the strain relief. SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 39: Connecting Up

    WARNING EXPLOSION HAZARD You may only connect or disconnect cables carrying electricity when the power supply is switched off or when the device is in an area without inflammable gas concentrations. SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 40: Industrial Ethernet

    Strain relief for the Ethernet cables In order to avoid mechanical stress on the Ethernet cables and resulting interruption of the contact, fasten the cables at a short distance from the connector using a cable guide or busbar. SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 41: Electrical

    IE switches causes an illegal loop. Such a loop can lead to network overload and network failures. Autonegotiation Autonegotiation means the automatic detection/negotiation of the transmission rate and the operating mode of ports at the opposite end. This makes it possible to configure different devices automatically. SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 42: Optical

    ● Close unused optical sockets and plugs as well as pluggable transceivers and slots with the supplied protective caps. Note No light power measurement (PROFINET diagnostics) The devices do not support diagnostics with light power measurement. SCRJ connector technology The attachment to Industrial Ethernet uses SCRJ connector technology. SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 43: Wiring Rules

    Crimp shapes with wave-shaped profile are unsuitable. Power supply Notes on the power supply WARNING Incorrect power supply Never operate the device to alternating voltage. Never operate the device with DC voltage higher than 32 VDC. SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 44 918 422 or a comparable protective element. Manufacturer: DEHN+SOEHNE GmbH+Co.KG, Hans-Dehn-Str.1, Postfach 1640, D92306 Neumarkt, Germany Operate the SCALANCE XF-200BA with suitable overvoltage protection. Information on the power supply ● The power supply is connected via two 2-pin plug-in terminal blocks that ship with the device.
  • Page 45: Signaling Contact

    The signaling contact can be subjected to a maximum load of 100 mA (safety extra‑low voltage SELV, 24 VDC). Higher voltages or currents can damage the device. Position and assignment Figure 5-2 Position of the signaling contact on the SCALANCE XF-200BA and the assignment of the terminal block Contact Assignment Fault contact 1...
  • Page 46: Grounding

    ● If you connect a communications node to an unmonitored port or disconnect it, this does not cause an error message. ● The signaling contact remains open until the error has been eliminated. Grounding The device is grounded over the DIN rail. SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 47: Upkeep And Maintenance

    Upkeep and maintenance Downloading new firmware using TFTP without WBM and CLI Firmware The firmware is signed and encrypted. This ensures that only firmware created by Siemens can be downloaded to the device. Procedure with Microsoft Windows Using TFTP, you can supply a device with new firmware even when it cannot be reached using WBM or CLI.
  • Page 48: Restoring The Factory Settings

    You can also reset the device to the factory defaults during operation, see section "SET button (Page 24)". Via the configuration You will find detailed information on resetting the device parameters using the WBM and CLI in the configuration manuals see also section "Introduction (Page 3)": SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 49: Technical Specifications

    Technical specifications SCALANCE XF-200BA technical specifications Technical specifications Attachment to Industrial Ethernet Slots for bus adapters Quantity Ports per bus adapter Connector Depending on the bus adapter Properties Half/full duplex, MDI‑X pinning Transmission speed 10 / 100 Mbps Optical data (basic device with corresponding bus adapters)
  • Page 50 Technical specifications 7.1 SCALANCE XF-200BA technical specifications Technical specifications Ambient temperature During opera‐ up to 2000 m ‑40 ℃ to +70 ℃ tion up to 3000 m ‑40 ℃ to +66 ℃ up to 4000 m ‑40 ℃ to +63 ℃...
  • Page 51: Cable Lengths

    0 to 100 m 6 dB max. permitted FO cable attenuation with fiber 3 dB link power margin Switching properties Switching properties Aging time Can be configured (default value: 30 seconds) Maximum frame size 1632 SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 52: Mechanical Stability (In Operation)

    8127 Note The number of SCALANCE XF-200BA modules connected in a line influences the frame delay. When a frame passes through the IE switch, this is delayed by the store-and-forward function of the SCALANCE XF-200BA by 10-130 microseconds (at 100 Mbps).
  • Page 53: Dimension Drawings

    Dimension drawings Note The dimensions are specified in mm. SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 54 Dimension drawings SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 55: Approvals

    You can check which of the following approvals have been granted for your product by the markings on the type plate. Current approvals on the Internet You will find the current approvals for the product on the Internet pages of Siemens Industry Online Support (https://support.industry.siemens.com/cs/ww/en/ps/15273/cert). Notes for the manufacturers of machines The devices are not machines in the sense of the EC Machinery Directive.
  • Page 56 ● On the data medium that ships with some products: – Product CD / product DVD – SIMATIC NET Manual Collection ● On the Internet pages of Siemens Industry Online Support (https:// support.industry.siemens.com/cs/ww/en/view/78381013) The SIMATIC NET products described in these operating instructions meet the requirements of the EU directive 2014/34/EU "Equipment and Protective Devices for Use in Potentially...
  • Page 57 Type of protection of the device The devices are approved for various types of protection. You can find the type of protection of your device and the IECEx certificate number on the nameplate. Permitted types of protection SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 58 Category 2G, 3G, 2D or 3D equipment. EMC directive (electromagnetic compatibility) The SIMATIC NET products described in these operating instructions meet the requirements of EU directive 2014/30/EU "Electromagnetic Compatibility" (EMC Directive). SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 59 ● UL 61010-2-201 (Industrial Control Equipment) ● ANSI/ISA 12.12.01-2007 ● CSA C22.2 No. 213-M1987 Approved for use in Cl. 1, Div. 2, GP A, B, C, D T4 Cl. 1, Zone 2, GP IIC T4 SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 60 * In modular devices, you can find the marking in the operating instructions for the BusAdapter used. CAUTION Use of controls or adjustments or performance of procedures other than those specified herein may result in hazardous radiation exposure. SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 61 The test was performed with a device and a connected communications partner that also meets the requirements of the standards listed above. When operating the device with a communications partner that does not comply with these standards, adherence to the corresponding values cannot be guaranteed. SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 62 Approvals SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 63: Index

    Factory setting, 24, 48 Signaling contact, 25, 45 Fault/error status, 25 SIMATIC NET glossary, 5 Firmware, 25, 47 SIMATIC NET manual, 5 Spring-loaded terminal, 45 Startup phase, 25, 48 System manual, 4, 34, 61 Glossary, 5 SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...
  • Page 64 Index Web Based Management (WBM), 28, 47 Weight, 50 Wiring, 43 Wiring rules, 45 SCALANCE XF-200BA Operating Instructions, 09/2018, C79000-G8976-C470-03...