Connecting The Motor Cable - Siemens SINAMICS S120 Operating Instructions Manual

Applications for cabinet modules, liquid-cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

5.3.2

Connecting the motor cable

A
B
Figure 5-3
1. Open the cabinet. Removed the covers in front of the connection panel for the motor cables
(connections U2/T1, V2/T2, W2/T3; X2).
2. Move or remove the base plate below the connection panel through which the motor cables
are fed.
3. Attach the PE protective conductor at the intended locations in the cabinet to the appropriate
connection with the ground symbol. Observe the torque of 50 Nm for M12.
Siemens Drives & PLCs
Applications for Cabinet Modules, liquid cooled
Operating Instructions, 04/2015, A5E35974555A
Frame sizes FX, GX, HX
Frame size JX
Connecting the motor cables
Electrical connection
5.3 Connection
81