ABB i-bus KNX FCA/S 1.1M Product Manual

Fan coil actuator
Table of Contents

Advertisement

Quick Links

®
ABB i-bus
KNX
Fan Coil Actuator FCA/S 1.1M
Product Manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB i-bus KNX FCA/S 1.1M

  • Page 1 ® ABB i-bus Fan Coil Actuator FCA/S 1.1M Product Manual...
  • Page 3: Table Of Contents

    Parameter Distinction between short and long operation – no ..80 3.2.9.2 Parameter Distinction between short and long operation – yes..84 3.2.10 Parameter window Input B ...............86 3.2.11 Parameter window Output ...............87 3.2.11.1 Parameter window - Time..............90 © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 4 Bus voltage recovery ..............145 4.4.2 Reset via bus................. 147 4.4.3 Download (DL)................148 4.4.4 Reaction on bus voltage failure ............. 149 4.4.5 Behaviour with bus voltage failure, recovery and download ..149 Priorities with, … ................153 © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 5 ABB i-bus KNX Contents 4.5.1 Valve HEATING/COOLING ............153 Fast heat up/cool down..............154 4.6.1 Heat up...................154 4.6.2 Cooling down .................155 Appendix Scope of delivery ................157 Status byte forced/operation.............158 Ordering information .................159 Notes ......................160 © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 7: General

    The application of the device is described using examples. This manual is divided into the following sections: Chapter 1 General Chapter 2 Device technology Chapter 3 Commissioning Chapter 4 Planning and application Chapter A Appendix © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 8: Note

    Danger These safety instructions are used if there is a danger for life and limb with inappropriate use. Danger These safety instructions are used if there is a danger to life with inappropriate use. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 9: Product And Functional Overview

    The actuator is a modular installation device with a module width of 4 space units in ProM Design for installation in the distribution board. The connection to the ABB i-bus is established using the front side bus connection terminal. The Fan Coil Actuator does not require an auxiliary voltage supply. The assignment of the physical addresses as well as the parameterisation is carried out with Engineering Tool Software ETS (from Version ETS2 V1.3a)
  • Page 10: Product Overview

    Functional overview FCA/S 1.1M Inputs Window contact Drip tray FCA/S 1.1M Outputs 16 A (10 AX) switch Electrical auxiliary heater Outputs 6 A switches 3 speed fan Outputs 0.5 A switches Valve HEATING Valve COOLING © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 11: Device Technology

    ETS 2 from version V1.3a or higher. ® The device is powered via the ABB i-bus and does not require and additional auxiliary voltage supply. The FCA/S 1.1M is operational after connection of the bus voltage.
  • Page 12: Electronic Outputs

    = ambient temperature 2.1.2 Binary inputs Rated values Number scanning voltage 32 V, pulsed scanning current 0.1 mA Scanning current I at switch on Maximum 355 mA Permissible cable length 100 m one-way, at cross-section 1.5 mm² © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 13: Fan Rated Current 6 A

    Switching of electric discharge lamps These switching performances are defined in the standard EN 60947-4-1 Contactors and motor-starters - Electromechanical contactors and motor-starters. The standard describes starter and/or contactors which previously preferably used in industrial applications. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 14: Rated Current Output 16 A

    Switching of electric discharge lamps These switching performances are defined in the standard EN 60947-4-1 Contactors and motor-starters - Electromechanical contactors and motor-starters. The standard describes starter and/or contactors which previously preferably used in industrial applications. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 15: Output Lamp Load 16 A

    If ETS3 is used a .VD3 type file must be imported. The user program can be found in the ETS2 / ETS3 at ABB/Heating, Cooling, Blower/Fan Coil Actuator 1-fold. The device does not support the closing function of a project or the KNX device in the ETS.
  • Page 16: Connection Schematics

    18 LED valve HEATING 19 Button valve HEATING 20 LED valve COOLING 21 Button valve COOLING 22 LED binary input A 23 Button binary input A 24 LED binary input B 25 Button binary input B © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 17: Dimension Drawing

    Commissioning requirements In order to commission the device, a PC with ETS (from ETS2 V1.3a or ® higher) as well as an interface to the ABB i-bus , e.g. via a KNX interface, is required. The device is ready for operation after connection to the bus voltage.
  • Page 18 The warranty expires if the device is opened. Foil keypad The manual control keys may not be operated with pointed or sharp-edged objects, e.g. screwdrivers or pens. This may damage the keypad. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 19: Commissioning

    Coil Actuator is used in conjunction with a room temperature controller for an individual room temperature control system. The room temperature controller sends a control variable which is used to control the fan speeds via the Fan Coil Actuator. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 20: Parameters

    Engineering Tool Software ETS from version ETS2 V1.3 or higher. The user program can be found in the ETS2 / ETS3 at ABB/Heating, Cooling, Blower/Fan Coil Actuator 1-fold. The following chapter describes the parameters of the RM/S 2.1 using the parameter windows.
  • Page 21: Parameter Window General

    After bus voltage recovery the device always waits for the send delay time to elapse before sending telegrams on the bus. Note The set switching delay does not act on the electronic outputs (valve HEATING/COOLING)! © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 22 The input is activated. A further parameter window is provided on the left half of the window. Note The inputs are equipped as binary inputs with contact scanning. The scanning voltage is provided by the device. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 23 0 or 1 0: The status messages are sent with the value 0. 1: The status messages are sent with the value 1. 0 or 1: The status messages are sent with the value 0 or 1. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 24: Parameter Window Manual

    If manual operation is disabled via the application program, there is no reaction and the device remains in the KNX operation state. If it has been disabled, LED is switched on or over after it has flashed for three seconds. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 25 The status is sent after a change. after request: The status is sent after a request. after a change or request: The status is sent after a change or a request. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 26 The speeds are indicated in the sequence: Fan speed 1 with LED , Fan speed 2 with LED , Fan speed 3 with LED . If none of the speed LEDs are on the fan is off. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 27 HEATING button indicates it by flashing (five hertz). The communication object Overload Valve HEATING is set again to the value 1. Note If the device is in Manual operation the acknowledgement function Overload is not available. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 28 The button is enabled. disabled: The button is disabled. Note By pressing the button the relay is toggled. The display indicates the contact state. LED on = contact closed LED off = contact opened © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 29: Parameter Window Control Input (Hvac)

    A correction curve which may be set will be ignored! Monitoring control values e.g. thermostat Options: yes: The communication object Fault control value is enabled. Hereby for example, a thermostat can be cyclically monitored. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 30 The status is sent after a change or a request. Control value after control fault in [0…100] % Options: 0…30…100 This control value in percent can be set with a control value fault should the control fail (emergency operation). © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 31: Hvac System - 1 Control Value/2-Pipe

    After bus voltage recovery the state which existed before bus voltage failure is set. HEATING: After bus voltage recovery the HEATING state is set. COOLING: After bus voltage recovery the COOLING state is set. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 32: Hvac-System - 1 Control Value/4-Pipe, With Switching Object

    1: As soon as a telegram with the value 1 is received, HEATING is activated and COOLING is deactivated. 0: As soon as a telegram with the value 0 is received, HEATING is activated and COOLING is deactivated. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 33: Hvac System - 2 Control Value/2-Pipe

    After bus voltage recovery the state which existed before bus voltage failure is set. HEATING: After bus voltage recovery the HEATING state is set. COOLING: After bus voltage recovery the COOLING state is set. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 34: Hvac-System - 2 Control Value/2-Pipe, With Switching Object

    After bus voltage recovery the state which existed before bus voltage failure is set. HEATING: After bus voltage recovery the HEATING state is set. COOLING: After bus voltage recovery the COOLING state is set. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 35 1: As soon as a telegram with the value 1 is received, HEATING is activated and COOLING is deactivated. 0: As soon as a telegram with the value 0 is received, HEATING is activated and COOLING is deactivated. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 36: Hvac System - 2 Control Value/4-Pipe

    After bus voltage recovery the state which existed before bus voltage failure is set. HEATING: After bus voltage recovery the HEATING state is set. COOLING: After bus voltage recovery the COOLING state is set. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 37: Parameter Window Multi-Level Fan

    (See. techn. data of the fan!) Option: Changeover switch Step switch The control of the fan is set with this parameter. The mode of fan control should be taken from the technical data of the fan. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 38 Fan speed on bus voltage recovery Options: unchanged unchanged: The fan speeds of the fan remain unchanged. OFF: The fan is switched off. 1, 2 or 3: The fan switches to fan speed 1, 2 or 3. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 39 The forced operation is not deactivated, by a download of the application program in which the fan type and the respective group addresses are retained. The forced operation is reset if an ETS reset has occurred. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 40 Options: yes: Automatic operation is enabled. Furthermore the parameter window Automatic operation, on page 46 appears. Enable direct operation Options: yes: Direct operation is enabled. Furthermore the parameter window Direct operation, on page 52 appears. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 41 Here you set which fan speed the fan uses to start from the OFF state. Minimum dwell period in switch on in s [1…65,535] Options: 1…5…65,535 This parameter defines the minimum dwell time in one of the switch on speeds. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 42 The parameterised minimum dwell time in the fan speed for automatic mode is ignored during manual operation. Accordingly, an immediate reaction to the manual operation is detected. The delay time with speed switch over remains active to protect the fan. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 43: Parameter Window - Status Messages

    This parameter defines whether the status of the current fan speed or the required fan speed is displayed. What is the current fan speed? The current fan speed is the speed at which the fan is actually operating. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 44 What is the required fan speed? The required fan speed is the fan speed which has to be achieved, e.g. when the transition and dwell times are completed. With option yes the following parameters appear in the parameter: © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 45 The status is updated but not sent. after a change: The status is sent after a change. after request: The status is sent after a request. after a change or request: The status is sent after a change or a request. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 46 “Status automatic” 1 bit Options: The communication object Status automatic is enabled with this parameter. Telegram value 1 = fan coil actuator is in automatic operation 0 = automatic operation switched off yes: An additional parameter appears: © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 47 The status is updated but not sent. after a change: The status is sent after a change. after request: The status is sent after a request. after a change or request: The status is sent after a change or a request. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 48: Parameter Window Automatic Operation

    Options: This parameter defines how to react to a telegram. 1: Automatic is activated by a telegram with value 1. 0: Automatic is activated by a telegram with value 0. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 49 Fan speed x threshold value. The result equals the new upper or lower threshold. Switch threshold top (switch on) = threshold value + hysteresis Switch threshold bottom (switch off) = threshold value + hysteresis © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 50 Behaviour when descending from speed 3: – Speed 3 transition at 14 % (< 30 % – hysteresis). – The new speed is 1 (15 % is between 10 and 20 %). – Accordingly speed 2 is omitted. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 51 3 (start-up speed) and then proceeds to fan speed 2 which is defined by the limitation. The actual required fan speed 1 will not be achieved due to the limitation. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 52 Important The priority is according to the listed sequence. The highest priority is assigned to limitation 1, e.g. Frost/Heat protection; the lowest priority is assigned to limitation 4, e.g. standby operation. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 53 2, 1, OFF: limited to speed 2, 1 and off. 3: limited to speed 3.* 3, 2: limited to speed 3 and 2. 3, 2, 1: limited to speed 3, 2 and 1. * The control value is ignored. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 54: Parameter Window Direct Operation

    The parameterised minimum dwell time in the fan speed for automatic mode is ignored during manual operation. Accordingly, an immediate reaction to the manual operation is detected. The delay time with speed switch over remains active to protect the fan. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 55 Each new switching command initiates a new calculation of the target speed. This means that a target speed changes by switching telegrams until this is achieved.. Enable communication object “Fan speed switch” 1 byte Options: yes: A 1 byte Switch speed communication object is enabled. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 56: Parameter Window Two-Level Fan

    Now a two speed fan is controlled via fan speeds 1 and 2. Fan speed 3 with all its parameters and options is now non-functional. Note Further parameters and their setting possibilities are described in parameter window multi-level fan, page 35. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 57: Parameter Window One-Level Fan

    If a fan with one speed is to be controlled, the option one-level must be selected. Fan speed on bus voltage failure Option: unchanged The behaviour of the fan on bus voltage failure is defined here. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 58 0: Forced operation is activated by a telegram with value 0. Behaviour with forced operation Options: unchanged This parameter defines how the fan should respond with forced operation. Enable automatic operation Options: yes: Automatic mode is enabled; an additional Automatic operation parameter window appears. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 59 Time in s [1…65,535 x 0.1] Options: 1…20…65,535 The fan is switched off using this delay. With option minimum time the following parameters appear: Time in s [1…65,535] Options: 1…20…65,535 The fan remains OFF for at least this time. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 60: Parameter Window - Status Messages

    The status is updated but not sent. after a change: The status is sent after a change. after request: The status is sent after a request. after a change or request: The status is sent after a change or a request. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 61 Enable communication object “Status automatic” 1 bit Options: The communication object Status automatic is enabled with this parameter. Telegram value 1 = automatic operation active 0 = automatic operation inactive yes: The following parameter appears: © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 62 The status is updated but not sent. after a change: The status is sent after a change. after request: The status is sent after a request. after a change or request: The status is sent after a change or a request. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 63: Parameter Window - Automatic Operation

    Here the threshold value at which switch on occurs is defined. If the value in the control value communication object is greater than or equal to the parameterised threshold value, it is switched on. If the value is less, then it is switched off. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 64 Limitation 2, e.g. for comfort operation Limitation 3, e.g. for night shutdown Limitation 4, e.g. for standby operation Speed ranges (limitations) are defined for the fan with the speed limitation function that may not be exceeded or undershot. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 65 There are the same parameters for each of the individual four limitations used to limit the fan speeds. The priority is according to the listed sequence. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 66 Fan speed with limitation 2 Fan speed with limitation 4 Options: inactive unchanged With this parameter you set which fan speed is set with active limitation, or which speed is not exceeded or undershot. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 67: Parameter Window Valve Heating - 3-Point, Opening And Closing

    The time should be taken from the technical data of the valve. Valve position on bus voltage failure in % [0…100] Note: unchanged The valve remains unchanged at its position with a bus voltage failure. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 68 The closing position is exceeded by 5 % of the total time, max. one minute. This function cannot be interrupted! Thereafter, the current valve position is approached and the adjustment counter is set to zero. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 69 With this parameter the number of operations (valve controls) after which automatic adjustment is undertaken can be set. Note All actions greater than zero (motor does not move) are counted. The number should be taken from the technical data of the valve manufacturer. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 70: Parameter Window Valve Heating - Continuous Pwm

    The valve is closed as soon as current flows in the control circuit. de-energised closed: The following parameter appears: Valve position on bus voltage failure Option: closed This option is intended as a marker. The valve remains closed at bus voltage failure. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 71 0 % (valve closed) to position 100 % (valve fully open). Note The time should be taken from the technical data of the valve and corresponds with the total runtime. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 72: Fast Heat Up/Cool Down

    For further information see: Fast heat up/cool down, page 154 Correct valve characteristic curve Option: If the option yes is set in the parameter, the parameter window Curve, page 76, in which the valve is set appears. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 73: Parameter Window - Function

    Enable communication object "Forced operation" 1 bit Options: yes: The 1 bit communication object Forced operation is enabled and can then be used for forced operation. Note The characteristic curve adjustment is also active with forced operation. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 74 The status is sent after a request. after a change or request: The status is sent after a change or a request. Object value with valve position > 0 Options: 1 byte: The following parameter appears: © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 75 Enable communication object "Status valve purge" 1 bit Options: yes: The 1 bit Status valve purge communication object is enabled. The status of the valve purge and the following additional parameters are visible via this communication object. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 76 The time is reset each time it is downloaded. The time is reset as soon as purging is completed. This can occur either through automatic purging or via the communication object Trigger valve purge. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 77 The purging cycle will restart if Purge cycle in weeks [1…12] is changed after the download. Reset purge cycle from control value in % [1...99] Options: 1…99 Hereby, the purge cycle from the set control value is reset. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 78: Parameter Window - Curve

    The characteristic curve adjustment is active with forced operation. Caution A parameterisation of the value pairs with the same control value leads to an undefined state and should be strictly avoided. Otherwise it can lead to destruction of the HVAC system. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 79 0…50…100 Valve position in % [0…100] Options: 0…50…100 Further value pair Options: yes: A further value pair can be set. Value pair 4 Control value in % [0...100] Options:0…50…100 Valve position in % [0…100] Options:0…50…100 © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 80: Parameter Window Valve Cooling

    The setting options of valve COOLING do not differentiate from those of valve HEATING. The descriptions of the parameter setting options and adjustable communication objects for the valve COOLING are described under parameter window Valve HEATING – 3-point, opening and closing, page 65. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 81: Parameter Window Input A

    The following drawing shows the function in detail: Without With distinction between distinction between short/long short/long Input signal Possible reaction to Possible reaction to the input signal the input signal is the time duration from where a long operation is detected. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 82: Parameter Distinction Between Short And Long Operation - No

    (falling edge) Options: TOGGLE no reaction terminate cyclic sending For each edge a definition is made to determine if the object value ON, OFF or TOGGLE is switched or if there should be no reaction. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 83 Example: Debounce time of the input signal for a detected edge: Input signal Detected pulse edge After detection of an edge on the input, further edges are ignored for the debounce time T © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 84 The send cycle time describes the time used between two cyclically sent telegrams. Activate minimum signal time with rising edge Options: yes: The following parameter is visible: in value x 0.1 s [1...65,535] Options: 1…65,535 © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 85 Example: Minimum signal time of the input signal for a detected edge: Input signal Detected pulse edge As only two edges remain stable for the minimum signal time , only these are detected as valid. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 86: Parameter Distinction Between Short And Long Operation - Yes

    OFF or TOGGLE is switched or if there should be no reaction. Long operation after … 0.3/0.4/0.5/0.6/0.8 s Options: 1/1.2/1.5 s 2/3/4/5/6/7/8/9/10 s Here the time period T after which an actuation is considered as a “long” operation is defined. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 87 Example: Debounce time of the input signal for a detected edge: Input signal Detected pulse edge After detection of an edge on the input, further edges are ignored for the debounce time T © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 88: Parameter Window Input B

    3.2.10 Parameter window Input B Input B does not differentiate from input A. The descriptions of the parameter setting options and adjustable communication objects for the Input B are described under Input A, page 78. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 89: Parameter Window Output

    The contact is opened with bus voltage failure. closed: The contact is closed with bus voltage failure. unchanged: No change of the contact position. Note The reaction on bus voltage failure, recovery and download is to be monitored. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 90 Enable function time Options: yes: An additional parameter window appears in which the staircase lighting time is programmed. At the same time the communication object block staircase lighting is enabled. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 91 0=closed, 1=open: A closed contact is represented by communication object value 0 and an open contact is represented by the value 1. Note The contact position, and thus the switch status can result from a series of priorities and links. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 92: Parameter Window - Time

    0, i.e. Enable function Time: The function Time is enabled and active after a bus failure. Note If the staircase light is disabled when the function Time is operational, the light will stay ON until it is switched OFF manually. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 93 Only after a renewed download of the application program is the staircase lighting time overwritten. How does the staircase light behave with bus voltage failure? The behaviour at bus voltage failure is determined by the parameter Reaction on bus voltage failure in the parameter window General. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 94 If the communication object receives a telegram with the value 1, the output is switched ON irrespective of the value of the communication object Switch and remains switched on until the communication object Permanent ON has the value 0. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 95: Commissioning Without Bus Voltage

    UP and DOWN to suit the fan speed. If the manual switchover button ( ) is pressed until the corresponding LED switches off, the device will switch off again. The LED indicates its current state. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 96: Communication Objects

    DPT 1.002 ® In order to regularly monitor the presence of the Fan/Fan Coil Actuator on the ABB i-bus a monitoring telegram can be sent cyclically on the bus. . The communication object is enabled if in the parameter Send object "In operation" in the parameter window General has been selected with yes.
  • Page 97: Manual Operation

    On this communication object the Fan Coil Actuator sends the information regarding whether it is in Manual operation or Operation via KNX. The status is sent after a change. Telegram value: 0 = operation via EIB/KNX” 1 = manual operation © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 98: Control Input

    Using this communication object the control value COOLING is predefined as a 1 byte % value. Telegram value: 0 % = OFF, no cooling 100 % = ON, largest control value, maximum cooling Not assigned. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 99: With Switching Object

    If the value 0 is set in the parameter: Telegram value: 0 = HEATING activated 1 = COOLING activated Note If communication object 32 Toggle HEATING/COOLING – Control input receives a value, the monitoring time is started. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 100: Communication Objects Hvac System 2 Control Values/2-Pipe

    Using this communication object the control value COOLING is predefined as a 1 byte % value. Telegram value: 0 % = OFF, no cooling 100 % = ON, largest control value, maximum cooling Not assigned. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 101: With Switching Object

    If the value 0 is set in the parameter: Telegram value: 0 = HEATING activated 1 = COOLING activated Note If communication object 32 Toggle HEATING/COOLING – Control input receives a value, the monitoring time is started. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 102 Using this communication object the control value COOLING is predefined as a 1 byte % value. Telegram value: 0 % = OFF, no cooling 100 % = ON, largest control value, maximum cooling Not assigned. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 103: Communication Object Fault Control Value

    If the object value Control value HEATING, Control value COOLING or Control value, HEATING/COOLING remains off for a parameterised time, a fault of the thermostat is assumed. If communication object 32 Toggle HEATING/COOLING – Control input receives a value, the monitoring time is started. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 104: Multi-Level Fan

    The following telegram values result: 1 byte value Hexadecimal Binary value bit Fan speed 76543210 00000000 0 (OFF) 00000001 Fan speed 1 00000010 Fan speed 2 00000011 Fan speed 3 >3 >03 >00000011 Values greater than 3 are ignored © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 105 The last telegram – in this case the OFF telegram of another fan speed – is always executed. Telegram value: 0 = fan OFF 1 = fan ON in speed 1 Speed 2 See communication object 11 Speed 3 See communication object 11 © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 106 Some fans require an ON telegram before you set a fan speed. Using the communication object Status fan ON/OFF, the fan can for example, be switched on centrally with a switch actuator via the main switch © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 107 Telegram value: 0 = fan speed OFF 1 = fan speed ON Status fan speed 2 See communication object 17 Status fan speed 3 See communication object 17 Not assigned. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 108 Telegram value: 0 = limitation x inactive 1 = limitation x active Limitation 2 See communication object 21 Limitation 3 See communication object 21 Limitation 4 See communication object 21 © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 109 It is possible to parameterise if a communication object value is only updated and not sent, sent on request, or only sent when changed. The communication object indicates the status of the automatic mode. Telegram value: 0 = inactive 1 = activated © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 110 Bit 0: If toggling between HEATING and COOLING is undertaken automatically using control variables, the status HEATING/COOLING is only switched in bit 0 if a value > 0 is received on the control value For further information see: Status byte forced operation, page 157 © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 111: One-Level Fan

    The last command – in this case the OFF telegram of another fan speed – is always executed. Telegram value: 0 = fan OFF 1 = fan ON 12… Not assigned. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 112 The valve position is independently programmable from the fan limitation. Telegram value: 0 = limitation x inactive 1 = limitation x active Limitation 2 See communication object 21 Limitation 3 See communication object 21 Limitation 4 See communication object 21 © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 113 It is possible to parameterise if a communication object value is only updated and not sent, sent on request, or only sent when changed. The communication object indicates the status of the automatic mode. Telegram value: 0 = inactive 1 = activated © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 114 Bit 0: If toggling between HEATING and COOLING is undertaken automatically using control variables, the status HEATING/COOLING is only switched in bit 0 if a value > 0 is received on the control value For further information see: Status byte forced operation, page 157 © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 115: Valve Heating

    1 = start valve purge, valve will be opened Note for value 0 A purge currently underway is interrupted. A purge not undertaken due to a higher priority will no longer be undertaken. The purge cycle with automatic purge will be restarted © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 116 Die Anzeige LED HEIZEN ( ) zeigt den gleichen Wert wie der Status an. Telegram value: 0…255 = valve position is displayed directly as a figure value At 0 = LED HEATING off At > 0 = LED HEATING on © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 117: Valve Cooling

    The valve COOLING does not differ from valve HEATING. The descriptions of the parameter setting options and the adjustable communication objects for the valve COOLING are described in parameter window Valve HEATING, page 65 or the communication objects Valve HEATING, page 113. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 118: Input A

    The communication object can be sent cyclically, e.g. for life sign monitoring of the sensor. It is important to note that the communication object can be written to externally. Thus, cyclic sending is interrupted or may not be possible. Telegram value: 0 = OFF 1 = ON © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 119 Enable communication object with "Long operation" 1 bit has been selected with yes. This additional communication object is assigned to the long actuation. Communication object Input A – Switch no longer reacts to a long operation. Telegram value: 0 = no 1 = yes © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 120: Input B

    Input B does not differentiate from input A. The descriptions of the parameter setting options and adjustable communication objects for the Input B are described under parameter window Input A, page 79 and communication objects Input A, page 116. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 121: Output

    ON. The device receives a switch telegram via the switch object. Permanent On becomes inactive after a download or bus voltage recovery. Telegram value 1 = activates Permanent ON 0 = deactivates Permanent ON © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 122 The communication object value directly indicates the current contact position of the switching relay. The status value can be inverted. Telegram value 1 = relay ON or OFF depending on the parameterisation 0 = relay OFF or ON depending on the parameterisation © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 123: Planning And Application

    The Fan Coil unit is connected to a central heating and cooling water supply and generates the desired temperature for the room. A room can be heated, cooled and ventilated using a Fan Coil unit. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 124: Fan Operation

    The output must be linked to the communication object Status Fan ON/OFF. Hereby, the main switch is switched on if at least one fan speed is set. If the fan is OFF (Status Fan ON/OFF = 0), the main switch is also switched off. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 125: Fan In A Two-Way Connection

    The step switch cannot be switched on rapidly. If for example, fan speed 3 is to be switched on from the OFF state, fan speeds 1 and 2 must be controlled with the associated dwell times first. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 126: Configuration Of A Hvac System With Fan Coil Units

    Filter Heat exchanger The fan blows air past the heat exchanger and into the room through a filter. The air is heated or cooled in the heat exchangers and thus generates the desired room temperature. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 127: Pipe Systems

    The water condensation which results during cooling collects in a condensation water trough. 4.1.5 Pipe systems A Fan Coil unit can be configured as a 2, 3 or 4-pipe system. 4-pipe version 3-pipe version 2-pipe version © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 128: Pipe System, Configuration

    In a 2-pipe Fan Coil unit there is only one heat exchanger with a valve. Note In some HVAC systems cooling is undertaken exclusively with a 2-pipe Fan Coil unit. The heating function is undertaken by a conventional heater or an electrical heater. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 129: 2-Pipe System Heating And Cooling

    Depending on this setting both control values act on just a single valve. The thermostat decides which control value (HEATING/COOLING) is actively sent. The FCA/S controls the fan speed and only one valve. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 130: 2-Pipe System Heating Or Cooling

    Both 2-pipe systems can be established using a 3 speed fan or blower. Depending on the control value (1 byte or 1 bit) which is sent from a thermostat, the Fan Coil Actuator determines the corresponding fan speeds via programmable threshold values. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 131: 3-Pipe System, Configuration

    In contrast to a 4-pipe system the 3-pipe system has a common return for heating and cooling water. The Fan Coil Actuator directly controls the fan and provides two communication objects for control of the valves. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 132: 4-Pipe System, Configuration

    COOLING, an additional signal decides if the system is in heating or cooling mode and the valve that has to be controlled. The Fan Coil Actuator directly controls the fan and provides two communication objects for control of the valves. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 133: System Configuration With A Fan Coil Actuator

    In order to correctly implement this function, the thermostat must send the actual temperature as well as the corresponding operating mode to the Fan Coil Actuator via the bus. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 134: Automatic Operation

    An activation of one of the four limitations or the forced operation does not end automatic operation. By using a range limit (several fan speeds are permissible), a limited automatic control with several fan speeds is possible. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 135 ABB i-bus KNX Planning and application The following functional diagram shows the relationship between automatic and manual operation of the Fan Coil Actuator. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 136: Direct Operation

    4.2.2 Direct operation ® With direct fan control via the ABB i-bus , a fan drive is connected directly to the Fan Coil Actuator and switched via three floating contacts. A single speed, two speed or three speed fan can be connected.
  • Page 137: Logic Of The Speed Switching

    The diagram relates to a three speed fan without parameterised fan limitations. The fan limitations are only relevant after the fan speed has been determined and do not change the flow chart. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 138: Fan Operation Functional Diagram

    The following illustration indicates the sequence in which the functions of the fan control are processed. Communication objects, which lead to the same box have the same priority and are processed in the sequence in which the telegrams are received. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 139: Valve Drives, Valves And Controller

    Depending on the variant, the valve is opened when voltage is applied and closed when no voltage is applied, or vice versa. Electro-thermal valve drives connected via two connection cables to the Fan Coil Actuator. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 140: Valve Curve

    These valve curves can be matched for different valve types. Many valves for example, have practically no flow when barely opened and achieve maximum flow at 60-80 %. Furthermore, many valves emit an annoying whistling sound at low flows. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 141 The positioning frequency of the valve drive may also be reduced by this limitation. Valve position 100 % Active valve opening range Valve control value 100 % Limitation of the active valve opening range © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 142 A reduction of the positioning frequency reduces the current requirement for positioning and increases the service life of the valve. However, a reduced positioning frequency will also impair the accuracy of the temperature control. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 143: Control Types

    Continuous control can be implemented with the Fan Coil Actuator for ® electro-motor 3-point or ABB i-bus valve drives. This is implemented via a 1 byte control. What is a 1 byte control? For 1 byte control, a value of 0…255 (corresponds to 0 %…100 %)
  • Page 144: Pulse Width Modulation (Pwm)

    Simple, attractively-priced control valves can be used. The positioning frequency of the control valve is relatively high. Pulse width modulation can be used with the Fan Coil Actuator in conjunction with electromotor or electro-thermal valve drives. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 145 20 %, then for a cycle time of 15 minutes the valve will be opened for three minutes (20 % of 15 minutes) and closed for 12 minutes (80 % of 15 minutes). © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 146: Pulse Width Modulation - Calculation

    Due to t = 0.4 x t the valve is set to about 40 % on. t is the so-called PWM cycle time for continuous control. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 147: Behaviour With

    If none of the two above options is selected, the last position is retained as with bus voltage failure. Note If a staircase lighting time was active at bus voltage failure, it will restart. Inputs The inactive waiting time is only active at bus voltage recovery. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 148 (with the exception of manual operation/reference run) was active before the failure. If during bus voltage recovery and an active priority a new control value is received, it will replace the Control value which was defined in the parameterisation. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 149: Reset Via Bus

    The switch contact output goes to the safely opened state. Note For all resets after delivery including the first download, the response will comply with that of a reset via the bus. A send and switch delay is not executed. All states are reset. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 150: Download (Dl)

    Otherwise the block for the function Time is removed, if the object Disable function time is not available. The switch contact output will otherwise use the new parameters. The object value Permanent ON remains unchanged. The switch contact output remains unchanged. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 151: Reaction On Bus Voltage Failure

    (unchanged) or to switch off. The special behaviour is described in the following table. 4.4.5 Behaviour with bus voltage failure, recovery and download © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 152 ABB i-bus KNX Planning and application © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 153 ABB i-bus KNX Planning and application © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 154 ABB i-bus KNX Planning and application © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 155: Priorities With

    The priorities are defined as follows: 1. Reference movement 2. Manual operation 3. Communication object Block 4. Communication object Forced operation 5. Valve purge 6. Adjustment 7. Control values Note 1 corresponds to the highest priority. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 156: Heat Up

    For a change in the lower % range it results in significantly shorter closing times than for changes in the upper % range. Thereafter the contact is opened in accordance with the new PWM cycle and the PWM cycle is started. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 157: Cooling Down

    For a change in the lower % range it results in significantly shorter opening times than for changes in the upper % range. Thereafter the contact is opened in accordance with the new PWM cycle and the PWM cycle is started. © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 159: Appendix

    The Fan Coil Actuator is supplied together with the following components. The delivered items should be checked according to the following list. 1 x FCA/S 1.1M, Fan Coil Actuator, MDRC 1 x installation and operating instructions 1 x bus connection terminal (red/black) © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 160: Status Byte Forced/Operation

    ABB i-bus KNX Appendix Status byte forced/operation = applicable © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 161: Ordering Information

    ABB i-bus KNX Appendix Ordering information Short description Designation Order No. bbn 40 16779 Price Weight Packaging group 1 pc. [pc.] [kg] FCA/S 1.1M Fan Coil Actuator, MDRC 2CDG 110 084 R0011 66508 7 © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 162: Notes

    ABB i-bus KNX Appendix Notes © 2010 ABB STOTZ-KONTAKT GmbH...
  • Page 164 With regard to purchase orders, the agreed Eppelheimer Straße 82 particulars shall prevail. 69123 Heidelberg, Germany ABB AG does not accept any responsibility Phone: +49 (0) 6221 701 607 whatsoever for potential errors or possible lack of E-mail: knx.marketing@de.abb.com information in this document.

Table of Contents