Control Circuit Terminals; Terminal Layout - Mitsubishi Electric 700 Series Installation Manualline

Hide thumbs Also See for 700 Series:
Table of Contents

Advertisement

3.3 Control circuit terminals

3.3.1 Terminal layout

A1
PC
AM
3.3.2 Instructions for wiring of the control circuit terminal
Terminals PC, 5, and SE are all common terminals (0V) for I/O signals and are isolated from each other. Avoid
connecting the terminal PC and 5 and the terminal SE and 5 (ground). Terminal PC is a common terminal for the contact
input terminals (STF, STR, STOP, RH, RM, RL, JOG, RT, MRS, RES,AU, CS).
Use shielded or twisted cables for connection to the control circuit terminals and run them away from the main and
power circuits (including the 230V relay sequence circuit)..
Use two or more parallel micro-signal contacts or twin
contacts to prevent a contact faults when using contact
inputs since the control circuit input signals are micro-
currents.
Do not apply a voltage to the contact input terminals (e.g. STF) of the control circuit.
Always apply a voltage to the alarm output terminals (A, B, C) via a relay coil, lamp, etc.
It is recommended to use the cables of 0.75mm
If the cable gauge used is 1.25mm
cables are run improperly, resulting in an operation panel contact fault.
The wiring length should be 30m maximum.
The level of the control signals can be switched over between positive (SOURCE) and negative (SINK) logic. The input
signals are set to source logic when shipped from the factory. To change the control logic, the jumper connector on the
control circuit terminal block must bemoved to the other position.
10
B1
C1
A2
B2
C2
10E
10
2
5
4
2
gauge for connection to the control circuit terminals.
2
or more, the front cover may be lifted when there are many cables running or the
RL
RM
RH
RT
AU
STOP
1
SE
RUN
SU
IPF
Micro signal contacts
CA SD PC
RES STF STR PC
OL
FU MRS JOG CS
Zwillingskontakte

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents