Inverter Type; Installation Of The Inverter - Mitsubishi Electric 700 Series Installation Manualline

Hide thumbs Also See for 700 Series:
Table of Contents

Advertisement

1 INSTALLATION

1.1 Inverter Type

Symbol
Voltage Class
Three-phase 400V
A740
class
Capacity plate example
Capacity plate
Inverter type

1.2 Installation of the inverter

Installation on the panel
00023 to 00620
.
Note
The internal filter is suitable for the second environment, a motor cable length of up to 5m and a carrier frequency of
up to 2kHz. For other operation conditions, Mitsubishi Electric offers several optional filters. Please contact your
sales representive.
Symbol
Type number
00023
Displays the
to
rated current
12120
Serial number
00770 to 12120
Fix six positions for the FR-A 740-
04320 to 08660 and fix eight positions
for the R-A 740-09620 to 12120.
Rating plate example
Rating plate
Inverter type
Input rating
Output rating
Serial number
Overload current rating
SLD
110% 60s, 120% 3s
LD
120% 60s, 150% 3s
ND
150% 60s, 200% 3s
HD
200% 60s, 250% 3s
CAUTION
When encasing multiple inverters, install them in parallel and
leave clearance as a cooling measure.
Install the inverter vertically.
*2
10 cm or more
*2
10 cm or more
*1 1 cm or more for 00126 or less
10 cm or more for 02160 or more
*2 20 cm or more for 02160 or more
Ambient temperature
40°C
50°C
50°C
50°C
vertic