Quick installation and start-up guide
FBIP-21 BACnet/IP adapter module

Safety instructions

WARNING! Obey the safety instructions. If you ignore them, injury or death, or damage to the
equipment can occur. See the user's manual.

Mechanical installation

1. Pull out the lock.
2. Install the module carefully to an option
module slot of the drive. See the drive
hardware manual.
3. Push in the lock.
4. Tighten the screw to torque 0.8 N·m using
a Torx TX10 screwdriver.
WARNING! Do not use excessive force,
or leave the screw too loose. Over-
tightening can damage the screw or
module. A loose screw decreases the EMC
performance, and can even cause an operation
failure.

Electrical installation

Layout of the module
6
2
3
1
5
4
1
No.
Description
1
Lock
2
Mounting and grounding screw
3
RJ-45 connector [X1] to Ethernet
4
RJ-45 connector [X2] for chaining another module
5
Diagnostic LEDs
6
MAC ID
3
4

Advertisement

loading

Summary of Contents for ABB FBIP-21

  • Page 1: Safety Instructions

    Options for ABB drives, converters and inverters Quick installation and start-up guide FBIP-21 BACnet/IP adapter module Safety instructions WARNING! Obey the safety instructions. If you ignore them, injury or death, or damage to the equipment can occur. See the user’s manual.
  • Page 2: Further Information

    To take the settings into use, validate and refresh the parameters with parameter 51.27 FBA par refresh. Further information See the latest version of FBIP-21 BACnet/IP adapter For more information on fieldbus options and protocols module user's manual (3AXD50000028468 [English]) in provided by ABB Drives, see the fieldbus ABB library (www.abb.com/drives/documents)