The device is self-ventilated and approved for inclined mounting at angles up to +/-35° in
stationary cabinets.
NOTICE
Damage due to overheating
Inclined installation reduces the convection by the device and therefore the maximum
permitted ambient temperature for operation.
If there is sufficient forced ventilation, the device can also be operated in the inclined
mounting position up to the maximum permitted ambient temperature for vertical
installation. The device may otherwise be damaged and its certifications and warranty will
be rendered null and void.
For information on permitted ambient temperatures, refer to the section Operating conditions
(Page 37).
Mounting position
Select one of the approved mounting positions for your device. The approved mounting
positions are described in the following sections.
Mounting in horizontal format
The device is intended for installation in landscape format.
A maximum ambient temperature of +45 °C is permissible for vertical installation.