Lenovo 46M4002 Installation And Maintenance Manual page 19

1u c19 and c13 switched and monitored pdus
Table of Contents

Advertisement

a. Leave enough space to connect, route, and disconnect power cords.
b. If you are installing a cable-management bracket in the same side of the rack cabinet, leave enough
space between the outlet side of the PDU and the EIA mounting flanges for the cable-management
bracket installation.
Attention: You must disconnect the main input power before you connect or disconnect the input
power cord from the PDU.
3. If the PDU comes with a detached power cord, connect the power cord. Align the connector on the
power cord that comes with the PDU with the connector on the front of the PDU, turning as necessary
for key alignment; then, turn the twist-lock on the connector clockwise until it locks into place.
.
Chapter 2
Installing the 1U PDU vertically in a rack cabinet
11