Chapter 8. PDU specifications

The tables in this chapter contain the product specifications of the PDUs.
The following table contains the descriptions of the PDUs. Match the numbers in the left column with the
numbers for the rated voltage, rated current, and maximum power rating in the other tables in this section.
Note: In the following table, the PDU option part number and the power cord option part number are shown
in parentheses.
1
DPI 32 amp / 250 V single-phase 1U 9 C19 / 3 C13 switched and monitored DPI PDU with IEC 309 P+N+Gnd
connector (46M4002; 40K9612)Note: Special connector for Australia and New Zealand (not IEC 309):
(46M4002; 40K9617)
2
DPI 60 amp / 208 V single-phase 1U 9 C19 / 3 C13 switched and monitored DPI PDU with IEC 309 2P+Gnd
connector (46M4002; 40K9615)
3
DPI 63 amp / 250 V single-phase 1U 9 C19 / 3 C13 switched and monitored DPI PDU with IEC 309 P+N+Gnd
connector (46M4002; 40K9613)
4
DPI 32 amp / 250 V three-phase 1U 9 C19 / 3 C13 switched and monitored DPI PDU with IEC 309 3P+N+Gnd
connector (46M4002; 40K9611)
5
DPI 30 amp / 208 V single-phase 1U 9 C19 / 3 C13 switched and monitored DPI PDU with NEMA L6-30P (2P
+Gnd) connector (46M4002; 40K9614)
5
DPI 30 amp / 208 V single-phase 1U 12 C13 switched and monitored DPI PDU with NEMA L6-30P (2P+Gnd)
connector (46M4004; 40K9614)
6
DPI 60 amp / 208 V three-phase 1U 9 C19 / 3 C13 switched and monitored PDU with IEC 309 3P+Gnd
connector (46M4003 with attached power cord)
6
DPI 60 amp / 208 V three-phase 1U 12 C13 switched and monitored PDU with IEC 309 3P+Gnd connector
(46M4005 with attached power cord)
7
DPI 60 amp / 208 V single-phase 1U 12 C13 switched and monitored DPI PDU with IEC 309 2P+Gnd connector
(46M4004; 40K9615)
8
DPI 32 amp / 250 V single-phase 1U 12 C13 switched and monitored DPI PDU with IEC 309 P+N+Gnd
connector (46M4004; 40K9612)Note: Special connector for Australia and New Zealand (not IEC 309):
(46M4004; 40K9617)
8
DPI 63 amp / 250 V single-phase 1U 12 C13 switched and monitored DPI PDU with IEC 309 P+N+Gnd
connector (46M4004; 40K9613)
9
DPI 32 amp / 250 V three-phase 1U 12 C13 switched and monitored DPI PDU with IEC 309 3P+N+Gnd
connector (46M4004; 40K9611)
13
DPI 30 amp / 250 V single-phase 1U 9 C19 / 3 C13 switched and monitored DPI PDU (with special Korea
connector) P+N+Gnd connector (46M4002; 40K9618)
Height
Width
Depth
Additional clearance
© Copyright Lenovo 2015, 2018
43.9 mm (1.73 in.)
447 mm (17.6 in.)
350 mm (13.78 in.)
25 mm (0.98 in.) for circuit breakers 3 mm
(0.12 in.) for outlets
55