Connection Resources For Routing; Table 3-12 Number Of Routing Connection Resources (For Dp/Pn Cpus) - Siemens CPU 31 Series Technical Data Manual

Table of Contents

Advertisement

Communication
3.3 S7 connections
3.3.4

Connection resources for routing

Number of connection resources for routing
The CPUs with DP interface provide a different number of connection resources for the
routing function:
Table 3-12
CPU
31xC, CPU 31x
317-2 DP
31x-2 PN/DP
319-3 PN/DP
Example of a CPU 314C-2 DP
The CPU 314C-2 DP provides 12 connection resources (refer to Table 3-11):
• Reserve two connection resources for PG communication.
• Reserve three connection resources for OP communication.
• Reserve one connection resource for S7-based communication.
This leaves six connection resources available for other communication service, e.g. S7
communication, OP communication, etc.
In addition 4 routing connections via the CPU are possible.
3-32
Number of routing connection resources (for DP/PN CPUs)
As of firmware version
2.0.0
2.1.0
2.2.0
2.4.0
Number of connections for routing
Max. 4
Max. 8
Interface X1 configured as:
MPI:Max. 10
DP master: Max. 24
DP slave (active): Max. 14
Interface X2 configured as:
PROFINET: Max. 24
Interface X1 configured as:
MPI: Max. 10
DP master: Max. 24
DP slave (active): Max. 14
Interface X2 configured as:
DP master: Max. 24
DP slave (active): Max. 14
Interface X3 configured as:
PROFINET: Max. 48
CPU 31xC and CPU 31x, Technical Data
Manual, 01/2006 Edition, A5E00105475-06

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents