INTRODUCTION
INSTALLATION
P/N 315-034870-4
The Model XMI from Siemens Industry, Inc., provides an interface between the
FireFinder-XLS/Desigo Fire Safety Modular/Cerberus PRO Modular system and the
MDACT Digital Alarm Communicator. Both the XMI and the MDACT must be in-
stalled in the same MOM-2 cardcage. Mounting plate Model MOM2-XMP is required
to install the MOM-2 into the FireFinder-XLS/Desigo Fire Safety Modular/Cerberus
PRO Modular enclosure models CAB-1/-2/-3. The XMI has two 60-pin receptacles for
the FireFinder-XLS/Desigo Fire Safety Modular/Cerberus PRO Modular data bus
allowing the MOM-2 containing the XMI to be installed into any module location in
the rear of a CAB-1/-2/-3. The XMI receives 24V power from the PSC-12 and produces
a local 5VDC and 24VDC for the MOM-2 which in turn provides power to the MDACT.
Remove all system power before installation, first battery, then AC. (To power up,
connect the AC first, then the battery.
The XMI and MDACT install into a CAB-1/-2/-3 using the MOM2-XMP mounting plate
and a MOM-2 card cage.
1.
Mount the MOM-2 (P/N 500-892766) to the MOM2-XMP (P/N 500-634822)
mounting plate using the screws supplied with the MOM2-XMP . The
MOM2-XMP adapts the MOM-2 to the module mounting locations in the
rear of the CAB-1/-2/-3. (Refer to Figure 1.)
2.
Configure the MDACT, refer to Installation Instructions P/N 315-099351.
3.
Install the MDACT into the MOM-2 in mounting slot P4. (Refer to Figure 1.)
4.
Install the XMI into the MOM-2 in mounting slot P2. (Refer to Figure 1.)
5.
Mount the MOM2-XMP on the CAB-MP in the rear of the CAB-1/-2/-3.
6.
Connect the 60-pin 12 inch ribbon cable (provided) from JP1to the previous
CC-5/CC-2/PSC-12/PSX-12. If the XMI is mounted on the first row and you
are connecting to a CC-5/CC-2/PSC-12/PSX-12 on the second row, use 60-
pin 42 inch ribbon cable P/N 599-633997 (not provided). (Refer to Figure 1.)
7 .
If required, use a second 60-pin ribbon cable to connect JP2 to the next
CC-5/CC-2/PSC-12/PSX-12. (Refer to Figure 1.)
Siemens
Siemens
Siemens Industry
Industry
Industry, , , , , Inc.
Siemens
Siemens
Industry
Building
Building
Building
Building
Building T T T T T ec
ec
ec
echnologies Di
ec
hnologies Division
hnologies Di
hnologies Di
hnologies Di
Industry
Inc.
Inc.
Inc.
Inc.
vision
vision
vision
vision

Advertisement

loading

Summary of Contents for Siemens XMI

  • Page 1: Installation Instructions

    MOM-2 containing the XMI to be installed into any module location in the rear of a CAB-1/-2/-3. The XMI receives 24V power from the PSC-12 and produces a local 5VDC and 24VDC for the MOM-2 which in turn provides power to the MDACT.
  • Page 2 60-pin ribbon cable (P/N 599-633997) from CC-5/CC-2/PSC-12/PSX-12 Figure 1 Installing the XMI Connect 24V from TB6 on the MOM-2 to 24V on the PSC-12 with 18AWG- 12AWG wire. (Refer to Figure 1.) ELECTRICAL RATINGS Refer to MDACT Installation Instructions, P/N 315-099351, for electrical ratings. Be sure to include the MDACT in PSC-12/PSX-12 power supply loading and battery calculations.
  • Page 3 Cyber security disclaimer Siemens products and solutions provide security functions to ensure the secure operation of building comfort, fire safety, security management and physical security systems. The security functions on these products and solutions are important components of a comprehensive security concept.
  • Page 4 Siemens Industry, Inc. Siemens Canada, Ltd. Building Technologies Division 1577 North Service Road East Florham Park, NJ Oakville, Ontario Document ID A6V10239134 P/N 315-034870-4 L6H 0H6 Canada...