Local operation
5.2
Operating elements of the service field (ISF)
Fig. 20: Commissioning and service field (ISF)
1 "Power" LED: Displays supply by line
voltage.
2 Accept button (100 %): Press to set the
current position as 100 %; press in
combination with the 4 button to end the
adjustment process.
By simultaneously pressing the 4 button
for at least 5 seconds you can switch the
actuator to manual mode (MAN).
(Software version 2.00 and higher)
3 Reset button: Press to restart the
processor. If the adjustment is not yet
terminated, the set end positions are
deleted.
4 Accept button (0 %): Press to set the
current position as 0 %; press in
combination with the 2 button to end the
adjustment process.
By simultaneously pressing the 2 button
for at least 5 seconds you can switch the
actuator to manual mode (MAN).
(Software version 2.00 and higher)
28
1
2
3
4
5
6
5 LED for 0% position: Depending on the
flash rate, this LED indicates either
adjustment, position saved, manual
mode (MAN) via digital input (software
version 2.00 or higher) or error.
6 Write-protection switch (default: OFF).
7 RS232 connector: Connection for a PC.
8 Potential switch: Connection of reference
potential either to system or protective
ground (default setting: to system).
9 Travel button: Press to initiate actuator
movement.
10 LED for 100 \% position: Depending on
the flash rate, this LED indicates either
adjustment, position saved, manual
mode (MAN) via digital input or graphic
user interface (software version 2.00 or
higher) or error.
OI/PME/LME/EAN823/EBN853/EBN861-EN
10
9
8
7
M00203