11.INSPECTION AND MAINTENANCE
To maintain the function and performance of the vacuum contactor for a long period
of time, the following inspections and maintenance procedures are recommended.
The intervals between inspections may vary depending on the conditions of use and
the environment under which the contactor is used. The initial inspection should be
carried out within one year of the start of equipment operation, and the succeeding
check intervals should be determined according to the result of the initial inspection.
See Section 2 for use under special environment as in outdoor cubicles.
(1) Patrol Inspection(every 1-6 months)
With the cubicle energized, visually check from out side the cubicle according to
the check list of Table 4,5.
WARNING : When opening the door of the cubicle, do not come close
Check item
Abnormal noise
Abnormal smell
Check item
Abnormal discoloration
Damage
Open/close indication
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
to danger area.
Table 4
Patrol inspection items
Check if corona discharges or operation
magnets are not producing noise.
Check if corona discharges or overheat are
not producing abnormal smell.
Table 5
Patrol inspection items(cont.)
Is there not any discoloration due to
overheat?
Is there not any crack, break or dislocation
of insulating material or operation tools?
Is the OPEN/CLOSE indication (lamp)
normal?
-
15 -
What to check
What to check
6F9G0154