Siemens CC62P User Manual page 17

Gas detection system for toxic and explosive gases
Table of Contents

Advertisement

Available languages

Available languages

bottom line shows the time, date and the event number according to the list -from 00 to 99-.
5.Press FORWARD to list all events: from the oldest to most recent. When it reaches the last one it will start
again from the top of the list.
6.Press ENTER to exit.
Numbered, dated and timed registered events:
• Module line connected.
• Module line disconnected.
• Engineer Programming Input.
• User Programming Input.
• Erasing Events.
• Power Fault.
• Power re-established.
• Battery Test Fail -9V when system is tested manually-.
• 9V Battery Low -automatically after a power fault-.
• Automatic Ventilation Enabled.
• Manual Ventilation Enabled.
• Stop Ventilation Enabled.
• 1st Speed Level.
• 2nd Speed Level (*).
• 1st Speed Ventilation Activated.
• 2nd Speed Ventilation Activated (*).
• Alarm Level.
• Saturation Level -equipment bottom of scale for the different gases-.
• Detector Error -communication fault-.
• Sensor Error -shortcircuit or disconnected in the 4-20mA interface-.
• Installation Overhaul from time to time.
• Installation Overhaul Completed.
• Average of 20 min (*).
• Average of 8 h (*).
• Group General Fault.
(*) Depending on the Standard
NOTE: When the maximum storage capacity is reached the latter events in the list will be overwritted the first.
4.6
This menu allows to print out all the events displayed.
1. Press PROGRAMMING to print out.
4.7
This menu allows to list the highest concentration of each group at any date and time.
1.Press PROGRAMMING.
2.Press FORWARD to see highest levels.
3.Press ENTER to exit.
Fire & Security Products
Siemens Building Technologies - 03.2012
Printing out events (with printer connected -optional-)
Seeing highest levels
17
SiemensUserMan-v03