C h a p t E R 7

Setting calibration parameters

Should configuration with the Easy Setup menu not be enough to meet your needs, you will have to
calibrate your instrument and enter specific values to perform this calibration. The following pages
explain how to do this.

Setting level calibration parameters

Level calibration parameters are set under the Calibrate menu. Figure 39 illustrates these parameters
Figure 38 The Calibrate menu

Changing the empty/zero value

This value (probably set initially from the Easy Setup menu) represents the lowest level measurement
value in your vessel.
To set that value:
1 Select Calibrate > Level Calibration > Empty/Zero.
2 Press Edit.
3 Set the value as necessary and press OK.
By default, the empty/zero value is linked to the 4 mA value.
NOTICE
Make sure that the empty value is less than or equal to the full value.