Operating instructions OI/LST100-EN Rev. AC
LST100
Ultrasonic level transmitter for upstream oil and gas
Accurately track and measure one
of the most expensive consumable
on a site – chemicals
Measurement made easy
Introduction
Keep track of chemical usage and stock
– No other instrument is able to monitor chemical levels
effectively in such an easy-to-use, compact device.
Track chemical usage and remotely monitor stock levels
for chemicals in all sites, no matter how remote.
Safe for use at all sites in potentially explosive
environments
– FM approved for use in Zone 2 or Div 2 applications
without a barrier, or Zone 1 or Div 1 using the
recommended intrinsic safety barrier.
Ultra-low power consumption for solar or battery
– The LST100 has ultra-low power consumption equivalent
to a 4 to 20 mA instrument functioning constantly at 4
mA. Using 1 to 5 V output means low power consumption
during all conditions.
– The LST100 is typically powered from a solar or battery
power source. Its low power consumption ensures low
cost of ownership.
For more information
Additional publications for the LST100 ultrasonic
level transmitter are available for free download
from
www.abb.com/level
or by scanning this code:

Advertisement

Table of Contents
loading

Summary of Contents for ABB LST100

  • Page 1 4 to 20 mA instrument functioning constantly at 4 mA. Using 1 to 5 V output means low power consumption during all conditions. – The LST100 is typically powered from a solar or battery power source. Its low power consumption ensures low cost of ownership.
  • Page 2: Table Of Contents

    4.4.1 Factory settings ........... 14 4.4.2 Commissioning using the Easy Setup menu .. 14 5 Configuration ............ 15 5.1 Menu navigation ........... 15 5.2 Parameter descriptions ......... 16 5.3 Downloading and uploading configurations .... 18 2 OI/LST100-EN | LST100 – Ultrasonic level transmitter...
  • Page 3: Safety

    The LST100 is designed with state-of-the-art technology and The operators must strictly observe the applicable national is operationally safe. It left the factory pre-tested for safety regulations with regard to installation, function tests, repairs, and in perfect working order.
  • Page 4: Plates And Symbols

    IMPORTANT (NOTE) This symbol indicates operator tips, particularly useful information or important information about the product or its further uses. The signal word “IMPORTANT (NOTE)” does not indicate a dangerous or harmful situation. 4 OI/LST100-EN | LST100 – Ultrasonic level transmitter...
  • Page 5: Name Plate

    Avertisement – Danger statique Nottoyez uniquement avec un chiffon humide Designed by ABB Engineering (Shanghai) Ltd. Manufactured by ABB Inc. 7051 Industrial Boulevard, Bartlesville, Oklahoma, USA Certification plate Fig. 1.1: Product labels LST100 – Ultrasonic level transmitter | OI/LST100-EN 5...
  • Page 6: Mounting

    2 Mounting 2.1 Installation requirements An LST100 level transmitter can be installed almost anywhere Dimensions in mm (in.) in the tank. Consider the following installation conditions: Ø 77.3 (3.0) – Ensure the instrument is installed within recommended 32 (1.3) temperature and pressure ratings.
  • Page 7: Mounting On A Tank Using The Mounting Bracket

    Hole Fig. 2.6: Securing the mounting bracket to the tank using the nut 4. Referring to Fig. 2.7, fit a seal to the LST100 transmitter and screw the transmitter into the bracket by hand. Note: Tighten the transmitter hand-tight only – do not use tools.
  • Page 8: Other Mounting Variations

    (for 20 ft. version) or 2 in. (for the 30 ft. version). the tank. 2. Fit a seal to the LST100 transmitter, insert the transmitter 2. Fit a seal to the LST100 transmitter and screw the through the hole and secure from inside the tank using transmitter into the sleeve by hand.
  • Page 9: Electrical Connection

    3.1 Cable connection area power supply. The LST100 does not support hot plugging for The electrical wiring is fitted to the LST100 using a 1/2-14 NPT all interfaces (1 to 5 V output, RS485). Installation engineers cable gland. To ensure the transmitter’s NEMA 4X and IP 67...
  • Page 10: Signal Cable Connection

    Do not connect the shielding to different grounds power supply is: 120 mW. at each end of the cable. 3.2.2 Analog output LST100 has a 1 to 5 V analog output that is connected using the terminals shown in Fig. 3.3. Test Ground (earth) –...
  • Page 11: Digital Communications

    – The baud rate of the LST100 transmitter’s RS485 communication is fixed at 9600 bps. – The LST100 supports cable lengths of up to 30 m (100 ft). LST100 – Ultrasonic level transmitter | OI/LST100-EN 11...
  • Page 12: Commissioning

    Vista onwards. For Windows-based computers using A Connect To dialog is displayed: Windows Vista or later, copy HyperTerminal from the flash drive that ships with the LST100 to any convenient location on the computer. An RS485 connection to the computer is required for setup but most modern computers are not fitted with RS485 serial communication ports.
  • Page 13 User name: Password: 5159 5. Click OK to exit connection configuration and return to the HyperTerminal window: Connection to the LST100 is established and the home screen of the transmitter is displayed. LST100 – Ultrasonic level transmitter | OI/LST100-EN 13...
  • Page 14: Commissioning The Unit

    The LST100 is delivered with default factory settings as see Section 5.2, Parameter descriptions . shown in Table 4.1, Factory default settings. 1. Log on to the LST100 as described in Section 4.1 of this manual. On the welcome screen are 5 menus: Easy, Calibration, Menu...
  • Page 15: Configuration

    The default value is according to the product specification. Adjusting Blanking is optional. Blanking After sending a command to the LST100, one of three responses are returned: Response status Description 8. On the Easy Setup menu, select 6 to configure Max Rate Invalid input The input value is out of range.
  • Page 16: Parameter Descriptions

    Enable user calibration function Measured Value of P1 0.001 to 15.24 m (0.003 to 50.00 ft) LST100 measured value of calibration point 1 (short range) Actual Value of P1 0.001 to 15.24 m (0.003 to 50.00 ft) Actual distance to target for calibration point 1 (short range) Measured Value of P2 0.001 to 15.24 m (0.003 to 50.00 ft)
  • Page 17 Read Only Indicate the the temperature is too low Noise Alarm Read Only Indicate the the average noise is above noise threshold Clear NV Load Error 1. No Clear NV load error LST100 – Ultrasonic level transmitter | OI/LST100-EN 17...
  • Page 18: Downloading And Uploading Configurations

    5.3 Downloading and uploading configurations To download a device configuration: To upload a device configuration: 1. Log on to the LST100 using the following logon information: 1. Log on to the LST100 using the following logon information: User name: LSTCONFIG...
  • Page 19 – Offset error The error at close range is equal to the error at maximum 1. Log on to the LST100 as described in Section 4.3, range. In this case the “c” value in the equation y=mx+c Configuring the digital communications . The welcome screen is displayed.
  • Page 20 IMPORTANT (NOTE) Step 9 is applicable only if Operate Mode was 5. Ensure the LST100 is measuring the long range calibration set to Level before calibration was performed. point and select 3. Monitor Console from the main menu.
  • Page 21 7 Diagnostic messages The LST100 provides several diagnostic messages that can be viewed from the menu. The diagnostic messages provide insight into the state of the current process and can be valuable when troubleshooting an application. Table 7.1 details each diagnostic message together with possible causes and remedial actions.
  • Page 22 EN 60529 (1989) to IP 66/67 or by NEMA 4X Power supply 3 terminals for power supply (PE/+/–): The LST100 operates from 9 to 16 V DC and is protected against reversed polarity Analog output (1 to 5 V) 2 terminals for analog output (+/–): 1 to 5 V related to level,...
  • Page 23 Notes LST100 – Ultrasonic level transmitter | OI/LST100-EN 23...
  • Page 24 Texas Offices notice. With regard to purchase orders, the agreed Toll-free: + 1 800 442 3097 3700 West Sam Houston particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or Quotes: totalflow.inquiry@us.abb.com Parkway South, Suite 600 possible lack of information in this document.