Page 1
A B B M E A S U R E M E N T & A N A L Y T I C S | O P E R A T I N G I N S T R U C T I O N TTF200 Field-mount temperature transmitter Measurement made easy Additional Information Additional documentation on TTF200 is available free of charge for downloading at www.abb.com/temperature. Alternatively, scan this code:...
Page 2
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A Short product description Field-mount temperature transmitter for the measurement of the temperature of liquid and gaseous measuring media. Additional Information Additional documentation on TTF200 is available free of charge for downloading at www.abb.com/temperature.
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A Contents Electrical connections ........16 6.3.1 Protection of the transmitter from damage Safety ................4 caused by highly energetic electrical General information and instructions ....4 interferences ............16 ...
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A Safety Intended use This device is intended for the following uses: General information and instructions — To measure the temperature of fluid, pulpy or pasty These instructions are an important part of the product and substances and gases or resistance/voltage values.
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A Notes on data security This product is designed to be connected to and to communicate information and data via a network interface. It is operator’s sole responsibility to provide and continuously ensure a secure connection between the product and your network or any other network (as the case may be).
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A Use in potentially explosive IECEx intrinsic safety atmospheres according to ATEX Approved for use in Zone 0, 1, and 2. and IECEx Model TTF200-H1 IECEx Certificate of Conformity IECEx PTB 09.0014X NOTICE Ex ia IIC T6...T1 Ga...
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A Temperature data Electrical data 2.2.1 Transmitter 2.3.1 Transmitter ATEX / IECEx intrinsic safety Intrinsic safety type of protection Ex ia IIC (part 1) Temperature class Permissible ambient temperature range Supply circuit Device category 1 Device category Max.
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A 2.4 Installation instructions Devices with the "Ex d" type of protection with cable 2.4.1 ATEX / IECEx glands The installation, commissioning, maintenance and repair of For devices with the "Ex d - flameproof enclosure" type of...
Page 9
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A Installation instructions M20 x 1.5 plastic cable gland for various types of The sealing rings of the cable glands harden at low protection temperatures. The M20 x 1.5 plastic cable gland (supplied on an optional Before installation, bring the sealing rings to a temperature basis) has a limited temperature range.
A Transmitter B Supply isolator / DCS input with supply / When using the device in areas that require the device segment coupler safety level EPL "Ga" (Zone 0), the TTF200 types must be installed with aluminum housings, protected against strong mechanical impacts or friction.
Page 11
Fig. 7 Fig. 5 A Sensor B Transmitter in Ex d-housing C Supply isolator A Sensor B Transmitter TTF200 C Supply isolator [Ex ib] D Fuse, 32 mA E Interface for LCD display D Interface for LCD display The power supply circuit of the transmitter must be limited The input for the supply isolator must have an [Ex ib] by an upstream fuse with a fuse current rating of 32 mA.
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A Flameproof enclosure - Zone 0 / 1 Commissioning Housing design: ATEX II 2G Ex d IIC T6 Gb The commissioning and parameterization of the device may Transmitter design: ATEX II 1G Ex ia IIC T6 Ga...
LCD display. The LCD display is used to visualize the current process values. NOTICE A configuration of the TTF200 with the type B LCD display with the configuration function used in the TTF300 is not possible. A11165 Fig.
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A 5 Transport and storage 6 Installation Inspection Check the devices immediately after unpacking for possible damage that may have occurred from improper transport. Details of any damage that has occurred in transit must be recorded on the transport documents.
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A Opening and closing the housing 6.2 Rotating the LCD indicator DANGER Danger of explosion if the device is operated with the transmitter housing or terminal box open! While using the device in potentially explosive...
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A 6.3 Electrical connections 6.3.1 Protection of the transmitter from damage caused by highly energetic electrical interferences DANGER The transmitter has no switch-off elements. Therefore, Improper installation and commissioning of the device overcurrent protective devices, lightning protection, or carries a risk of explosion.
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A The following items should be observed to protect the 6.3.4 Shielding of the sensor connection cable transmitter from sensor-side damage: To ensure the system benefits from optimum — In the vicinity of the transmitter, sensor and sensor...
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A 6.3.5 Examples of shielding / grounding Insulated sensor measuring inset (thermocouple, mV, RTD, ohms), transmitter housing grounded The shielding of the sensor connection cable is grounded via the grounded transmitter housing. This shielding is insulated from the sensor.
Page 19
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A Insulated sensor measuring inset (thermocouple, mV, RTD, ohms), transmitter housing not grounded The shielding of the power supply cable and the shielding of the sensor connection cable are connected to one another via the transmitter housing.
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A 6.3.6 Pin configuration A11164 Fig. 20 A Potentiometer, four-wire circuit B Potentiometer, three-wire circuit C Potentiometer, two-wire circuit D RTD, four-wire circuit E RTD, three-wire circuit F RTD, two-wire circuit G Voltage measurement H Thermocouple I 4 … 20 mA HART J Interface for type BS LCD display K Ground terminals for sensor and supply/signal line shield support 1 –...
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A 6.3.8 Electrical data for inputs and outputs Input - thermocouples / voltages Input - resistance thermometer / resistances Types Resistance thermometer — B, E, J, K, N, R, S, T in accordance with IEC 60584 —...
Page 22
Fig. 22: Maximum load depending on input terminal voltage A TTF200 B TTF200 in Ex ia design C HART communication resistance Maximum power consumption — P = U x 0.022 A...
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A Commissioning HART Communication Terminals + / - General remarks Manufacturer ID 0x1A In case of corresponding order the transmitter is ready for Device Type ID 0x0D operation after mounting and installation of the Profile HART 5.1...
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A 7.4.1 Parameter descriptions DTM menu path, parameters Description <Device> / <Extras> <Write Protection> Activates write protection for the entire device — Yes: locked — No: unlocked — Enter password: 0110 <Device reset>...
Page 25
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A DTM menu path, parameters Description <Device> / <Configuration> <Sensor / Connection> Sensor connection type relevant for all Pt, Ni, Cu resistance thermometers — Two-wire: sensor connection type in two-wire technology — Three-wire: sensor connection type in three-wire technology —...
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A 7.4.2 Factory settings The transmitter is configured at the factory. The table below contains the relevant parameter values. Menu Designation Parameter Factory setting Device Setup Write protection Input Sensor Type Pt100 (IEC60751)
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A Basic Setup 7.5.2 D/A analog output adjustment (4 and 20 mA 7.5.1 Sensor error adjustment (DTM Adjustment trim) function) D/A analog output adjustment is used to compensate for Sensor error adjustment can be performed in the DTM by errors in the current input of the higher-level system.
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A 8 Operation 7.5.3 HART variables The transmitter provides three HART variables. The HART Safety instructions variables are assigned the following values: If there is a chance that safe operation is no longer possible, —...
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A 9 Diagnosis / error messages 8.2.1 Error messages on the LCD display If the event of an error, a message consisting of a symbol or letter (device status) and a number (DIAG NO.) will appear at the bottom of the process display.
Values overshot Check parameters: A) Sensor limits overshot B) Span is too small NOTICE If the remedial measures listed for the error message do not improve the status of the device, please consult ABB Service. Change from one to two columns...
WEEE directive 2012/19/EU — If it is not possible to dispose of old equipment properly, ABB Service can take receipt of and dispose of returns for a fee. 11 Repair 11.1 Returning devices...
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A 15 Declaration of conformity NOTICE Declarations of conformity of the device are available in the download center of ABB at www.abb.com/temperature. They are additionally enclosed with the device for ATEX certified devices.
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A 16 Appendix Return form Statement on the contamination of devices and components Repair and / or maintenance work will only be performed on devices and components if a statement form has been completed and submitted.
Page 36
We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.