Page 1
Introduction Additional Information — TTF200 The TTF200 with the 4 to 20 mA output and HART Additional documentation on TTF200 is available for communications protocol has global approvals download free of charge at for explosion protection up to Zone 0.
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B Table of contents Change from one to two columns Electrical connections ..........17 Safety ................3 General information and instructions ........3 Safety instructions ..............17 ...
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B 1 Safety Warnings General information and instructions The warnings in these instructions are structured as follows: These instructions are an important part of the product and must be retained for future reference.
/ or theft of data or information. • When using as a SIL-device in safety-relevant applications, ABB Automation Products GmbH and its affiliates are not liable the SIL Safety Manual should be observed. for damages and / or losses related to such security breaches,...
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B 2 Use in potentially explosive atmospheres in accordance with ATEX and IECEx Change from one to two columns Note IECEx intrinsic safety • Further information on the approval of devices for use in Approved for use in Zone 0, 1, and 2.
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B … 2 Use in potentially explosive atmospheres in accordance with ATEX and IECEx Temperature data Electrical data Transmitter Transmitter ATEX / IECEx intrinsic safety Intrinsic safety type of protection Ex ia IIC (Part 1)
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B Installation instructions ATEX / IECEx Type of protection flameproof (enclosure) Ex db IIC The installation, commissioning, maintenance and repair of devices in potentially explosive atmospheres must only be Supply circuit carried out by appropriately trained personnel. Works may be...
Page 8
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B … 2 Use in potentially explosive atmospheres in accordance with ATEX and IECEx Installation instructions for cable glands Maintenance The sealing rings of the cable glands harden at low Check the cable glands during each maintenance session. If the temperatures.
Risk of explosion! When using the device in areas that require the device safety Figure 3: Intrinsic safety installation check level EPL ‘Ga’ (Zone 0), the TTF200 types must be installed with aluminum housings, protected against strong mechanical impacts or friction.
Page 10
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B … 2 Use in potentially explosive atmospheres in accordance with ATEX and IECEx … Electrical connections ATEX - Zone 1 (0) ATEX - Zone 1 (20) Marking: II 2 (1) G Ex [ia IIC Ga] ib IIC T6 Gb...
Page 11
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B Flameproof (enclosure) - Zone 1 Housing design: ATEX II 2G Ex db IIC T6/T4 Gb The transmitter must be connected using suitable cable and Ex area Zone 1 Safe area cable entries or pipeline systems that satisfy the requirements of EN 60079-1 and for which a separate examination certificate exists.
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B … 2 Use in potentially explosive atmospheres in accordance with ATEX and IECEx Commissioning Repair DANGER The commissioning and parameterization of the device may also be carried out in potentially explosive atmospheres using a...
The LCD indicator is used to visualize the current element used in the measuring inset. process values. Note A configuration of the TTF200 with the type B LCD indicator with the configuration function used in the TTF300 is not possible. 1 Manufacturer, manufacturer k Client configuration:...
Page 14
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B … 4 Product identification … Name plate Explosion protection marking for devices with one type of Measures required before the use of devices with combined protection types of protection Devices with an explosion-proof design are marked with the following additional plates.
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B 5 Transport and storage 6 Installation Inspection Check the devices immediately after unpacking for possible damage that may have occurred from improper transport. Details of any damage that has occurred in transit must be recorded on the transport documents.
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B … 6 Installation Rotating the LCD indicator Opening and closing the housing DANGER Danger of explosion if the device is operated with the transmitter housing or terminal box open! While using the device in potentially explosive atmospheres...
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B 7 Electrical connections Protection of the transmitter from damage Safety instructions caused by highly energetic electrical interferences DANGER Explosion hazard The transmitter has no switch-off elements. Therefore, Improper installation and commissioning of the device carries overcurrent protective devices, lightning protection, or voltage a risk of explosion.
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B … 7 Electrical connections … Protection of the transmitter from Shielding of the sensor connection cable damage caused by highly energetic To ensure the system benefits from optimum electromagnetic electrical interferences interference immunity, the individual system components, and the connection cables in particular, need to be shielded.
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B Examples of shielding / grounding Insulated sensor measuring inset (thermocouple, mV, RTD, ohms), transmitter housing grounded The shielding of the sensor connection cable is grounded via the grounded transmitter housing. This shielding is insulated from the sensor.
Page 20
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B … 7 Electrical connections … Shielding of the sensor connection cable Insulated sensor measuring inset (thermocouple, mV, RTD, ohms), transmitter housing not grounded The shielding of the power supply cable and the shielding of the sensor connection cable are connected to one another via the transmitter housing.
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B Pin assignment A11164-01 A Potentiometer, four-wire circuit H Thermocouple B Potentiometer, three-wire circuit I Sensor terminals (of measuring inset) C Potentiometer, two-wire circuit J 4 to 20 mA HART® D RTD, four-wire circuit...
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B … 7 Electrical connections Terminal for sensor connection cable Electrical data for inputs and outputs Input - resistance thermometer / resistances DANGER Resistance thermometer Danger of explosion if the device is operated with the •...
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B Input - thermocouples / voltages Output Types Note B, E, J, K, N, R, S, T in accordance with IEC 60584 • The HART protocol is not secure, as such the intended •...
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B … 7 Electrical connections … Electrical data for inputs and outputs Power supply Voltage drop on the signal line Two-wire technology, polarity safe; power supply lines = signal When connecting the devices, note the voltage drop on the lines signal line.
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B 8 Commissioning General In case of corresponding order the transmitter is ready for The device is listed with the FieldComm Group. operation after mounting and installation of the connections. The parameters are set at the factory.
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B … 8 Commissioning Parameterization of the device Note The device does not have operating elements for parameterization on site. Parameterization takes place via the HART interface. Parameterization of the device takes place via standard HART®...
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B Parameter descriptions DTM menu path, parameters Description <Device> / <Extras> <Write Protection> Activates write protection for the entire device • Yes: locked, entry combination: ≠ 0110 • No: unlocked, entry combination: 0110 <Device reset>...
Page 28
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B … 8 Commissioning … Parameterization of the device DTM menu path, parameters Description <Device> / <Configuration> <Sensor / Reference junction> • Internal: use of the internal reference junction of the transmitter when using a thermocouple / compensating cable (relevant for all thermocouples except for type B) •...
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B Factory settings The transmitter is configured at the factory. The table below contains the relevant parameter values. Menu Designation Parameter Factory setting Device Setup Write protection Input Sensor Type Pt100 (IEC60751) R-Connection...
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B … 8 Commissioning Basic Setup Sensor error adjustment (DTM adjustment function) D / A analog output adjustment (4 mA- and 20 mA-Trim) Sensor error adjustment can be performed in the DTM by D/A analog output adjustment is used to compensate for errors navigating to the menu path Device / Calibration.
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B 9 Operation Safety instructions HART variables If there is a chance that safe operation is no longer possible, take the device out of operation and secure it against The transmitter provides three HART variables. The HART unintended startup.
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B … 9 Operation 10 Diagnosis / error messages … Process display The transmitter signals messages and errors in different ways. Error messages on the LCD display Messages via the HART interface If the event of an error, a message consisting of a symbol or letter (device status) and a number (DIAG NO.) will appear at the...
Check parameters: • Sensor limits up-scaled • Measuring span is too small Note If the remedial measures listed for the error message do not improve the status of the device, please consult ABB Service. Change from one to two columns...
All devices delivered to ABB must be free from any hazardous materials (acids, alkalis, solvents, etc.). When using the device in potentially explosive atmospheres, observe the notice on cleaning in Protection against Please contact Customer Center Service acc.
Service can take care of its pick-up and disposal for a fee. 14 Specification Note The device data sheet is available in the ABB download area at www.abb.com/temperature. 15 Additional documents Note Declarations of conformity of the device are available in the download area of ABB at www.abb.com/temperature.
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B 16 Appendix Return form Statement on the contamination of devices and components Repair and/or maintenance work will only be performed on devices and components if a statement form has been completed and submitted.
Page 37
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B Trademarks HART is a registered trademark of FieldComm Group, Austin, Texas, USA...
Page 38
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B Notes...
Page 39
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B Notes...
Page 40
We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.