Resetting the D/A trim
To reset the 4 – 20 mA trim:
1 Select Calibrate > 4-20 mA D/A Trim > Reset D/A Trim.
2 Press OK. The D/A trim is reset.
Setting a current simulation
To validate that calibration was successful, you can simulate a current output.
To perform the simulation:
1 Select Calibrate > 4-20 mA D/A Trim > Current Simulation.
2 Press Edit.
3 Set a current value (between 3.5 mA and 23.6 mA) that you want the instrument to generate and
press OK.
The ammeter should have a reading identical to the value entered.
Setting calibration parameters
63