Diagnostic Addresses For Dp Master And Dp Slave - Siemens SIMATIC S7-300 Series Reference Manual

Cpu specifications
Hide thumbs Also See for SIMATIC S7-300 Series:
Table of Contents

Advertisement

CPU 31x-2 as DP Master/DP Slave and Direct Communication
Diagnostic Addresses
With a CPU 31x-2, you assign the diagnostic addresses for the PROFIBUS-DP.
Make sure during configuration that DP diagnostic addresses are assigned to both
the DP master and the DP slave.
CPU 31x-2 as DP Master
During configuration you must specify two diagnostic
addresses:
Diagnostic
address
When you configure the DP master, you
must specify (in the associated project of
the DP master) a diagnostic address for
the DP slave. In the following, this
diagnostic address is referred to as
allocated to the DP master.
The DP master receives information on
the status of the DP slave or on a bus
interruption via this diagnostic address
(see also Table 2-3).
Figure 2-3

Diagnostic Addresses for DP Master and DP Slave

2-10
CPU 31x-2 as DP Slave
PROFIBUS
Diagnostic
address
When you configure the DP slave, you
must also specify (in the associated
project of the DP slave) a diagnostic
address that is allocated to the DP slave.
In the following, this diagnostic address
is referred to as allocated to the DP
slave.
The DP slave receives information on
the status of the DP master or on a bus
interruption via this diagnostic address
(see also Table 2-8 on page 2-23).