SUN2000-(2KTL-5KTL)-L0
User Manual
No.
Component
E
4G module
F
Smart Power Sensor
G
AC switch
Table 5-2 Cable description
No.
Cable
1
DC input
power cable
Issue 01 (2018-08-30)
The SUN2000 is embedded with a residual current monitoring unit (RCMU). Only a
single-phase circuit breaker or a similar AC load breaking device is required to function as
the external AC switch (shown by G in
safely disconnected from the power grid.
If the external AC switch can perform earth leakage protection, the rated leakage action
current should be greater than or equal to 100 mA.
If multiple SUN2000s connect to the general residual current device (RCD) through their
respective external AC switches, the rated leakage action current of the general RCD
should be greater than or equal to the number of SUN2000s multiplied by 100 mA.
A knife switch cannot be used as an AC switch.
Type
Standard PV cable in the
industry (recommended
model: PV1-)
Copyright © Huawei Technologies Co., Ltd.
Description
The 4G module that can connect to
the SUN2000 is Smart
Mobile-4G-EU.
The Smart Power Sensor that can
connect to the SUN2000 are
DDSU666-H, DTSU666-H,
CHINT-DDSU666,
CCS-WNC-3Y-400-MB,
Gavazzi-EM340DINAV23XS1X,
Gavazzi-EM112DINAV01XS1X,
and
Gavazzi-EM111DINAV81XS1X.
Recommended: a single-phase AC
circuit breaker with a rated voltage
greater than or equal to 250 V AC
and a rated current of
25 A (SUN2000-2KTL-L0 and
SUN2000-3KTL-L0)
32 A (SUN2000-4KTL-L0 and
SUN2000-5KTL-L0)
Figure
Conductor
Cross-sectional
Area Range
2
4–6 mm
5 Electrical Connections
Source
Can be purchased from
Huawei
Purchased by the customer
Purchased by the customer
5-1) to ensure that the SUN2000 can be
Outer
Diameter
4.5–7.8 mm
Source
Purchased by
the customer
38