Huawei SUN2000-50KTL-M0 Quick Manual

Huawei SUN2000-50KTL-M0 Quick Manual

Hide thumbs Also See for SUN2000-50KTL-M0:

Advertisement

Quick Links

SUN2000-(50KTL, 60KTL, 65KTL)-M0
Quick Guide
Issue: 05
Part Number: 31509437
Date: 2019-06-20
HUAWEI TECHNOLOGIES CO., LTD.

Advertisement

Table of Contents
loading

Summary of Contents for Huawei SUN2000-50KTL-M0

  • Page 1 SUN2000-(50KTL, 60KTL, 65KTL)-M0 Quick Guide Issue: 05 Part Number: 31509437 Date: 2019-06-20 HUAWEI TECHNOLOGIES CO., LTD.
  • Page 2: Product Overview

    Use insulated tools when installing the device. For personal safety, wear proper personal protective equipment (PPE). • Huawei shall not be liable for any consequence caused by violation of the storage, moving, installation, and operation regulations specified in this document and the user manual. Product Overview...
  • Page 3: Mounting Bracket Dimensions

    Indicator Status Description Alarm/Mainten Blinking red at long intervals (on for A warning alarm is ance indicator 1s and then off for 4s) generated. Blinking red at short intervals (on for A minor alarm is Alarm status 0.5s and then off for 0.5s) generated.
  • Page 4: Installation Requirements

    Installation Requirements Installation Angle Installation Space NOTE For ease of installing the SUN2000 on the mounting bracket, connecting cables to the bottom of the SUN2000, and maintaining the SUN2000 in future, it is recommended that the bottom clearance be between 600 mm and 730 mm.
  • Page 5 NOTE You are advised to apply anti-rust paint on the hole positions for protection.
  • Page 6: Installing Cables

    Installing Cables Installation Preparations NOTE • Before installing cables, ensure that all required OT terminals and cables are prepared. • The following table lists only recommended cable specifications. For more cable specifications, see the user manual. Model/ Name Description Specifications •...
  • Page 7: Opening The Maintenance Compartment Door

    Installing the Ground Cable • The ground point on the enclosure is preferred to connect to the PE cable for the SUN2000. • The ground point in the maintenance compartment is mainly used for connecting to the ground cable included in the multi-core AC power cable. For details, see section " 4.4 Installing AC Output Power Cables."...
  • Page 8: Installing Ac Output Power Cables

    If the screws on the enclosure door are lost, obtain spare screws from the fitting bag bound to the inductor cover at the bottom of the enclosure. Position for saving spare screws 3. Remove the cover and hang it on the hook of the enclosure door. Installing AC Output Power Cables •...
  • Page 9 3. Remove an appropriate length of the jacket and insulation layer from the AC output power cable using a wire stripper. (Ensure that the jacket is in the maintenance compartment.) a. Three-core cable (excluding the ground b. Four-core cable (including the ground cable cable and neutral wire) but excluding the neutral wire) Core...
  • Page 10 5. Connect the AC output power cable to the terminal block, and then tighten the nut using a torque wrench that has an extension rod. • Ensure that AC terminations provide firm and solid electrical connections. Failing to do so may cause SUN2000 malfunction and damage to its terminal block, even starting thermal events.
  • Page 11: Installing Dc Input Power Cables

    SUN2000-65KTL-M0 a. Three-core cable (excluding the ground b. Four-core cable (including the ground cable) cable) 6. Tighten the thread-lock sealing nut. 7. Clear debris from the maintenance compartment. Installing DC Input Power Cables Selecting DC Input Terminals NOTE The SUN2000 provides two DC switches, named as DC SWITCH 1 and DC SWITCH 2. DC SWITCH 1 controls the 1st to 6th sets of DC input terminals, whereas DC SWITCH 2 controls the 7th to 12th sets of DC input terminals.
  • Page 12 1. Use the Amphenol Helios H4 PV connectors provided with the SUN2000. If the terminals are lost or damaged, purchase the PV connectors of the same model. The device damaged caused by incompatible PV connectors is not covered under any warranty or service agreement.
  • Page 13: Installing The Rs485 Communications Cable

    Installing a DC Input Power Cable (Using Metal Stamping Forming Contacts) Positive metal contact Positive connector H4TC0003 Negative metal contact Negative (Amphenol) connector Recommended: PV cable Click Ensure that the cable that meets the 1100 V cannot be removed after standard.
  • Page 14 Terminal Block Connection (Recommended) 1. Remove an appropriate length of the jacket and core wire insulation layer from the communications cable using a wire stripper. 2. Route the cable through the cable gland. 3. Remove the cable terminal base from the terminal block.
  • Page 15 • When connecting the shielded cable, choose whether to crimp the OT terminal based on site requirements. • Tie the communication cables with the cables on internal side of the maintenance compartment. 6. Tighten the thread-lock sealing nut and seal the cable gland. RJ45 Network Port Connection 1.
  • Page 16: Optional) Installing The Solar Tracker Power Cable

    Tie the communication cables with the cables on internal side of the maintenance compartment. 5. Tighten the thread-lock sealing nut and seal the cable gland. (Optional) Installing the Solar Tracker Power Cable The solar tracker power cable can be installed on the SUN2000-65KTL-M0 only. 1.
  • Page 17 4. Connect the solar tracker power cable. 5. Install the shielding cover on wiring terminals. 6. Bind the solar tracker power cable. 7. Tighten the thread-lock sealing nut and seal the cable gland.
  • Page 18: Verifying The Installation

    The app name is SUN2000. 2. Access Huawei application store (https://appstore.huawei.com), Google Play (https://play.google.com), or App Store (iOS), search for SUN2000, and download the app installation package.
  • Page 19 WLAN or Bluetooth Connection USB Data Cable Connection Android iOS and Android Select Connection Login Page Select User Quick Settings Mode Function Menu • The screenshots in this document correspond to app version 2.2.00.050 (Android). • When the WLAN connection is used, the initial name of the WLAN hotspot is Adapter-WLAN module SN, and the initial password is Changeme.
  • Page 20 Huawei Technologies Co., Ltd. Huawei Industrial Base, Bantian, Longgang Shenzhen 518129 People's Republic of China www.huawei.com...

This manual is also suitable for:

Sun2000 seriesSun2000-60ktl-m0Sun2000-65ktl-m0