Page 1
SUN2000-(50KTL-M0, 70KTL-INM0) User Manual (India Edition) Issue Date 2019-07-30 HUAWEI TECHNOLOGIES CO., LTD.
Page 2
Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
About This Document About This Document Purpose This document describes the SUN2000-50KTL-M0 and SUN2000-70KTL-INM0 (SUN2000 for short) in terms of its installation, electrical connections, commissioning, maintenance, and troubleshooting. Before installing and operating the SUN2000, ensure that you are familiar with the features, functions, and safety precautions provided in this document.
Huawei. The safety precautions provided in this document do not cover all the safety precautions. Huawei shall not be liable for any consequence caused by the violation of the safety operation regulations and design, production, and usage standards.
Page 11
(C) ACDU (D) Step-up transformer (E) Power grid Supported Power Grid The SUN2000-50KTL-M0 supports the following power grids: TN-S, TN-C, TN-C-S, TT, and IT. The SUN2000-70KTL-INM0 supports the IT power grid only. Figure 2-3 Supported power grid Issue 03 (2019-07-30)
SUN2000-(50KTL-M0, 70KTL-INM0) User Manual (India Edition) 2 Overview 2.3.2 Product Nameplate Figure 2-4 Nameplate of the SUN2000-50KTL-M0 (1) Trademark, product name, and model (2) Important technical specifications number (3) Compliance symbols (4) Company name and place of production The nameplate figure is for reference only.
SUN2000 immediately disconnects from the power grid. If an AC switch that can detect residual current is installed outside the SUN2000-50KTL-M0, the residual current value to trigger the switch should be greater than 550 mA.
Page 44
If you connect a ground cable to the ground point in the maintenance compartment in a scenario with no neutral wire, you are advised to use a four-core (L1, L2, L3, and PE) outdoor cable as the AC output power cable for the SUN2000-50KTL-M0. ...
SUN2000-(50KTL-M0, 70KTL-INM0) User Manual (India Edition) 5 Electrical Connections Figure 5-18 SUN2000-50KTL-M0 (including the ground cable and neutral wire) The cable colors shown in figures are for reference only. Select an appropriate cable according to the local standards. Step 6 Tighten the cable gland.
Page 108
< 3% distortion (rated power) Note a: The rated output voltage of the SUN2000-50KTL-M0 is determined by Grid code, which can be set on the SUN2000 app, SmartLogger, or NetEco. Note b: Choose whether to connect the neutral wire to the SUN2000-50KTL-M0 based on the application scenario.