Panasonic U-4LE1R8 Service Manual page 10

Mini vrf system, r410a
Table of Contents

Advertisement

2. Settings of Outdoor Unit Control PCB
Examples of the No. of indoor units settings
No. of indoor units
1 unit (factory setting)
2 units
9 units
Examples of refrigerant circuit (R.C.) address settings (required when link wiring is used)
System address
No.
System 1 (factory setting)
1
System 11
System 21
System 30
<General Explanation of the Switches on the Outdoor Unit Control PCB>
MODE (3P)
Changes the operating mode (heating/cooling). (Can be used only at the main unit.)
During normal operation: Short-circuiting these pins once will change all indoor units in that
system to either cooling mode or heating mode.
During automatic address setting: When the pins are not connected, the mode is heating mode.
A. ADD (2P)
Short-circuited for 1 second or longer → Automatic address setting begins when the pins are
released. Short-circuiting these pins for 1 second or longer while automatic address setting is in
progress interrupts automatic address setting.
CHK (2P)
When these pins are short-circuited, the mode is test run mode. (Test run mode is automatically
canceled after 1 hour.) When the pins are released, test run mode is canceled.
RC (3P, blue)
The outdoor unit maintenance remote controller can be connected here to check the alarm
(CN-RC)
details.
RUN (2P)
Short-circuit these pins and apply a pulse signal to start all indoor units in that system.
STOP (2P)
Short-circuit these pins and apply a pulse signal to stop all indoor units in that system.
(If the pins are left short-circuited, it will not be possible to start operation from the indoor unit
remote controllers.)
AP (2P)
These pins are used when applying vacuum to the outdoor unit.
Socket for silent
Used for installing the external timer for the silent mode.
mode
(Refer to Section 1-14. Servicing and Maintenance Functions in Service Manual.)
2P plug (White)
(CN-SILENT)
Indoor unit setting (S004)
(Rotary switch, gray)
set to 1
set to 2
set to 9
System address
(S003)
(2P DIP switch, black)
(Rotary switch, yellow)
ON
ON
Both OFF
1
2
OFF
ON
ON
1 ON
1
2
OFF
ON
ON
2 ON
1
2
OFF
ON
ON
1 & 2 ON
1
2
OFF
System address
(S002)
set to 1
set to 1
set to 1
set to 0
1-4
Mini VRF SYSTEM
Address Settings