Download Print this page

ABB CV-1 Instruction Leaflet

Voltage relay
Hide thumbs Also See for CV-1:

Advertisement

Quick Links

Effective:
January 1997
Supersedes I.L. 41-201R, Dated April 1995
( | )
Denotes Change Since Previous Issu
This instruction leaflet applies to the following
types of relay:
CV-1 Long Time Undervoltage Relay
CV-2 Short Time Undervoltage Relay
CV-4 Long Time Overvoltage Relay
CV-5 Short Time Overvoltage Relay
CV-6 Long Time Over or Undervoltage Relay
CV-7 Short Time Over or Undervoltage Relay
CV-8 Low Voltage Pickup Overvoltage Relay
!
CAUTION
Before putting relays into service, remove all
blocking which may have been inserted for the
purpose of securing the parts during ship-
ment, make sure that all moving parts operate
freely, inspect the contacts to see that they
are clean and close properly, and operate the
relay to check the settings and electrical con-
nections.
1.
APPLICATION
The Type CV Relays are single-phase induction disc
type relays operating either on under or overvoltage
or both. These relays are applied as a voltage fault
detector operating in conjunction with other protec-
All possible contingencies which may arise during installation, operation or maintenance, and all details and
variations of this equipment do not purport to be covered by these instructions. If further information is
desired by purchaser regarding this particular installation, operation or maintenance of this equipment, the
local ABB Power T&D Company Inc. representative should be contacted.
Printed in U.S.A.
ABB Power T&D Company Inc.
Power Automation and Protection Division
Coral Springs, FL 33065
e
tive relays. The relays are also used as timing
devices for various automatic operations.
2.
The types CV-1, CV-2 CV-4, CV-5, CV-6, and CV-7
relays consist of a voltage unit and an indicating con-
tactor switch (ICS). The principal component parts of
the relay and their location are shown in Figures 1, 2,
and 3.
The Type CV-8 relay in addition to the above compo-
nents also has a capacitor which is series tuned with
the main coil of the electromagnet. This tuned circuit
offers a low impedance to fundamental current and a
high impedance to third harmonic currents. Hence,
the relay has a low pickup value for fundamental volt-
age and a much higher value of pickup for third har-
monic voltage. At rated voltage the electromagnet is
saturated causing the circuit to be detuned. The
impedance of the circuit is increased and limits the
fundamental current to a safe value.
2.1. Voltage Unit (CV)
The overvoltage unit operates on the induction disc
principle. A main tapped coil located on the center
leg of an "E" type laminated structure produces a flux
which divides and returns through the outer legs. A
shading coil causes the flux through the left leg (front
view) to lag the main pole flux. The out-of-phase
fluxes thus produced in the air gap causes a contact
closing torque.
The undervoltage unit operates on the same princi-
ple as the overvoltage unit except the shading coil is
on the right leg (front view). This causes the out-of-
phase fluxes to produce a contact opening torque.
Type CV
Voltage Relay
CONSTRUCTION AND OPERATION
Instruction Leaflet
I.L. 41-201S

Advertisement

loading

Summary of Contents for ABB CV-1

  • Page 1 This instruction leaflet applies to the following CONSTRUCTION AND OPERATION types of relay: The types CV-1, CV-2 CV-4, CV-5, CV-6, and CV-7 CV-1 Long Time Undervoltage Relay relays consist of a voltage unit and an indicating con- CV-2 Short Time Undervoltage Relay tactor switch (ICS).
  • Page 3 Normal the switch. When the switch closes, the moving con- operation of the two relays is such that the CV-1 and tacts bridge two stationary contacts, completing the CV-2 under-voltage relay will open its contacts with trip circuit.
  • Page 4 I.L. 41-201S voltage. With application of voltages greater than tap value voltage, the moving contact moves to close the front contact in a time as shown by the right-hand curves of either Figures 15 or 16. When the relay is used as an undervoltage relay, the moving contact is made with the stationary front contact for values of applied voltage greater than tap value voltage.
  • Page 5: Energy Requirements

    To use the position on the terminal plate in which the The 60 Hz burdens of the CV-1, CV-2, CV-4, CV-5, nylon screw is used, remove the nylon screw and CV-6, CV-7 relays at rated voltage are as follows: place it in one of the unused holes.
  • Page 6 I.L. 41-201S Sub 3 Sub 3 182A726 182A743 Internal Schematic Of The Type CV-8 199 Internal Schematic Of The Type CV-8 67 Figure 6. Figure 7. Volt Relay In Type FT-11 Case Volt Relay In Type FT-21 Case Sub 2 Sub 2 188A307 185A038...
  • Page 7: Installation

    3% condition. turning the proper nut with a wrench. b) CV-1 and CV-2 Undervoltage Relays For detailed FT Case information refer to I.L. 41-076. The moving contact should leave the backstop...
  • Page 8 I.L. 41-201S Where the resistor is used, the pickup setting the relay has been taken apart for repairs, or the can be adjusted from approximately 8% to 30% adjustments have been disturbed. This procedure of the continuous voltage rating. This setting is should not be used until it is apparent that the relay is made by adjusting the resistor.
  • Page 9: Renewal Parts

    I.L. 41-201S b) CV-1 and CV-2 Undervoltage Relays c) CV-6 and CV-7 Over or Undervoltage Relay Adjust the control spring tension so that the mov- Apply the indicated voltage of Table 1 and mea- ing contacts will leave the backstop of the time sure the operating time.
  • Page 10 I.L. 41-201S Curve 619537 Typical Time Curves Of The Type CV-8 Low Pickup Overvoltage Relay Figure 10a.
  • Page 11 I.L. 41-201S Curve 619541 Typical Time Curves For Type CV-8 Overvoltage Relay With Resistor Set For Maximum Pickup Figure 10b.
  • Page 12 I.L. 41-201S TYPICAL TIME CURVES TYPE CV-1 UNDERVOLTAGE RELAY 50/60 HERTZ TIME DIAL SETTING PERCENT TAP VALUE VOLTAGE Curve 418251 Typical Time Curves Of The Type CV-1 Long Time Undervoltage Relay Figure 11.
  • Page 13 I.L. 41-201S TYPICAL TIME CURVES TYPE CV-2 UNDERVOLTAGE RELAY 50/60 HERTZ TIME DIAL SETTING PERCENT TAP VOLTAGE VALUE Curve 418250 Typical Time Curves Of The Type CV-2 Short Time Undervoltage Relay Figure 12.
  • Page 14 I.L. 41-201S PERCENT OF TAP VALUE VOLTAGE Curve 406C881 Typical Time Curves Of The Type CV-4 Long Time Overvoltage Relay Figure 13.
  • Page 15 I.L. 41-201S Curve 406C884 Typical Time Curves Of The Type CV-5 Long Time Overvoltage Relay Figure 14.
  • Page 16 Curve 406C882 Typical Time Curves Of The Type CV-6 Long Time Over And Undervoltage Relay Figure 15.
  • Page 17 Curve 406C883 Typical Time Curves Of The Type CV-7 Short Time Over And Undervoltage Relay Figure 16.
  • Page 18 Sub 2 Curve 418270 Typical Sensitivity vs. Frequency Curve For Type CV-8 Low Pickup Overvoltage Relay Figure 17.
  • Page 19 I.L. 41-201S Sub 2 Sub 2 183A023 183A024 Diagram Of Test Connections Of The Type Diagram Of Test Connections Of The Type Figure 18. Figure 19. CV Undervoltage Relay CV Overvoltage Relay...
  • Page 20 * Sub 20 57D7900 Outline And Drilling For FT-11 Case Used For Projection And/or Semi-flush Case Figure 20. Printed in U.S.A. ABB Power T&D Company Inc. 4300 Coral Ridge Drive Coral Springs Florida 33065 954-752-6700 FAX: 305-345-5329...

This manual is also suitable for:

Cv-2Cv seriesCv-6Cv-7Cv-8Cv-4 ... Show all