Mitsubishi Electric CITY MULTI PFFY Series Technical & Service Manual
Mitsubishi Electric CITY MULTI PFFY Series Technical & Service Manual

Mitsubishi Electric CITY MULTI PFFY Series Technical & Service Manual

Floor standing type, indoor unit, exposed/concealed type, for use with the r410a & r22
Hide thumbs Also See for CITY MULTI PFFY Series:

Advertisement

Air-Conditioners For Building Application
TECHNICAL & SERVICE MANUAL
Series PFFY
<Indoor unit>
PFFY-P06NRMU-E,PFFY-P08NRMU-E
Models
PFFY-P12NRMU-E,PFFY-P15NRMU-E
PFFY-P18NRMU-E,PFFY-P24NRMU-E
PFFY-P06NEMU-E,PFFY-P08NEMU-E
PFFY-P12NEMU-E,PFFY-P15NEMU-E
PFFY-P18NEMU-E,PFFY-P24NEMU-E
Exposed type

Floor Standing Type

Concealed type
CONTENTS
SAFETY PRECAUTIONS ·························1
1. FEATURES ···········································3
2. PART NAMES AND FUNCTIONS ········4
3. SPECIFICATION ···································6
4. OUTLINES AND DIMENSIONS············8
5. WIRING DIAGRAM ·····························10
7. TROUBLE SHOOTING ·······················12
8. DISASSEMBLY PROCEDURE ··········· 17
For use with the R410A & R22
2014

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric CITY MULTI PFFY Series

  • Page 1: Table Of Contents

    2014 Air-Conditioners For Building Application TECHNICAL & SERVICE MANUAL Floor Standing Type Series PFFY <Indoor unit> PFFY-P06NRMU-E,PFFY-P08NRMU-E Models PFFY-P12NRMU-E,PFFY-P15NRMU-E PFFY-P18NRMU-E,PFFY-P24NRMU-E PFFY-P06NEMU-E,PFFY-P08NEMU-E PFFY-P12NEMU-E,PFFY-P15NEMU-E PFFY-P18NEMU-E,PFFY-P24NEMU-E CONTENTS SAFETY PRECAUTIONS ·························1 1. FEATURES ···········································3 2. PART NAMES AND FUNCTIONS ········4 3. SPECIFICATION ···································6 4. OUTLINES AND DIMENSIONS············8 5.
  • Page 2: Safety Precautions

    - Inadequate strength may cause the unit to fall down, resulting in is shorted and operated forcibly, or parts other than those specified injuries. by Mitsubishi Electric are used, fire or explosion may result. • Use the specified cables for wiring. Make the connections se- curely so that the outside force of the cable is not applied to the •...
  • Page 3 Precautions for devices that use Warning: • Note the following when building a heater in the air R410A refrigerant conditioning system. - Leave enough space between units for proper ventilation so that Caution: the indoor unit temperature does not exceed 40˚C when •...
  • Page 4: Features

    FEATURES Series PFFY Floor Standing Type Exposed type Concealed type Cooling capacity/Heating capacity Models BTU / h 1.8 / 2.0 6000 / 6700 PFFY-P06NEMU-E,PFFY-P06NRMU-E 2.3 / 2.6 8000 / 9000 PFFY-P08NEMU-E,PFFY-P08NRMU-E 3.5 / 4.0 12000 / 13500 PFFY-P12NEMU-E,PFFY-P12NRMU-E 4.4 / 5.0 15000 / 17000 PFFY-P15NEMU-E,PFFY-P15NRMU-E 5.3 / 5.9...
  • Page 5: Part Names And Functions

    PART NAMES AND FUNCTIONS ● Indoor (Main) Unit Air outlet Air outlet Air inlet Air inlet Exposed type Concealed type ● Remote controller [PAR-21MAA] ● Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button. [Operation buttons] TEMP.
  • Page 6 [Display] CENTRALLY CONTROLLED 1Hr. ON OFF CLOCK CHECK FILTER CHECK MODE TEST RUN STAND BY ERROR CODE FUNCTION NOT AVAILABLE DEFROST TEMP. ON/OFF A Current time/Timer B Centralized control C Timer OFF D Timer indicator E Operation mode: COOL, DRY, AUTO, FAN, HEAT...
  • Page 7: Specification

    SPECIFICATION 3-1. Specification PFFY-P-NEMU-E Model PFFY- PFFY- PFFY- PFFY- PFFY- PFFY- Item P06NEMU-E P08NEMU-E P12NEMU-E P15NEMU-E P18NEMU-E P24NEMU-E Power sourse 208/230V, 60Hz Cooling Capacity BTU/h 6000 8000 12000 15000 18000 24000 Heating BTU/h 6700 9000 13500 17000 20000 27000 Height 24-13/16 1050 1170...
  • Page 8 3-2. Electrical parts specification Model PFFY-P06 PFFY-P08 PFFY-P12 PFFY-P15 PFFY-P18 PFFY-P24 Symbol Parts NEMU-E NEMU-E NEMU-E NEMU-E NEMU-E NEMU-E name NRMU-E NRMU-E NRMU-E NRMU-E NRMU-E NRMU-E Tranrsformer (Primary) 60Hz 208-230V (Secondary) (23.5V 0.9A) Room Resistance 0˚C[32˚F]/15kΩ,10˚C[50˚F]/9.6kΩ,20˚C[68˚F]/6.3kΩ,25˚C[77˚F]/5.4kΩ, temperature TH21 30˚C[86˚F]/4.3kΩ,40˚C[104˚F]/3.0kΩ thermistor Liquid pipe Resistance 0˚C[32˚F]/15kΩ,10˚C[50˚F]/9.6kΩ,20˚C[68˚F]/6.3kΩ,25˚C[77˚F]/5.4kΩ, TH22...
  • Page 9: Outlines And Dimensions

    OUTLINES AND DIMENSIONS PFFY-P06·08·12·15·18·24NEMU-E Unit:mm(in.)
  • Page 10 PFFY-P06·08·12·15·18·24NRMU-E Unit:mm(in.)
  • Page 11: Wiring Diagram

    WIRING DIAGRAM PFFY-P06·08·12·15·18·24NRMU(NEMU)-E...
  • Page 12: Refrigerant System Diagram

    REFRIGERANT SYSTEM DIAGRAM Gas pipe thermistor TH23 Gas pipe Liquid pipe thermistor TH22 Flare connection Heat exchanger Linear expansion valve Strainer (#100mesh) Strainer (#100mesh) Room temparature thermistor TH21 mm <in.> Capacity PEFY-P06,08,12,15NEMU-E PEFY-P18NEMU-E PEFY-P24NEMU-E PEFY-P06,08,12,15NRMU-E PEFY-P18NRMU-E PEFY-P24NRMU-E Item ø ø R410A 12.7(1/2) 15.88(5/8)
  • Page 13: Trouble Shooting

    TROUBLE SHOOTING 7-1. How to check the parts Parts name Check points Room temparature Disconnect the connector, then measure the resistance using a tester. thermistor (TH21) (Surrounding temperature 10°C~30°C[50°F~86°F]) Liquid pipe thermistor (TH22) Normal Abnormal Gas pipe thermistor (Refer to the thermistor characteristic graph (TH23) 4.3kΩ...
  • Page 14 <Thermistor Characteristic graph> < Thermistor for lower temperature > Room temparature thermistor(TH21) Thermistor for Liquid pipe thermistor(TH22) lower temperature Gas pipe temparature thermistor(TH23) Drain sensor(DS) =15kΩ ± 3% Thermistor R Fixed number of B=3480kΩ ± 2% Rt=15exp { 3480( 273+t 0˚C 32˚F 15kΩ...
  • Page 15 <Output pulse signal and the valve operation> Output Output : 1 → 2 → 3 → 4 → 1 (Phase) Closing a valve Opening a valve : 4 → 3 → 2 → 1 → 4 ø1 The output pulse shifts in above order. ø2 ✻...
  • Page 16 7-2. Setting of address switch Make sure that power source is turning off. Indoor unit control board S W 2 S W 3 S W 4 < At delivery (All models)> S W 4 < At delivery (All models)> 1 2 3 4 5 6 7 8 9 10 0 1 2 3 4 5 6 7 8 9 9 10...
  • Page 17 7-3. Function of Dip-switch Operation by switch Switch Pole Function Remarks Thermistor<Intake temperature Indoor unit Built-in remote controller Address board detection>position Filter clogging detection Provided Not provided <At delivery> Filter life 2,500hr 100hr 1 2 3 4 5 6 7 8 9 10 Air intake Effective Not effective...
  • Page 18: Disassembly Procedure

    DISASSEMBLY PROCEDURE 8-1 CONTROL BOX (Exposed type PFFY-NEMU) Be careful removing heavy parts. OPERATING PROCEDURE PHOTOS 1.Removing the front panel (A) Fig.1 (1)Remove the fixing screws(two) of the front panel(A).(Fig.1) (2)Hold the bottom of the front panel with your hands,and gently lift it. The front panel should fall down forward.(Fig.2) 2.Removing the control box cover (B) (1)Remove the fixing screws(two) of the cover(B) and...
  • Page 19 8-2 THERMISTOR (Gas and liquid piping temperature detection) Be careful removing heavy parts. OPERATING PROCEDURE PHOTOS 1.Removing the side casing (1)Open the control panel cover(A), remove the fixing screws(two) of the securing cover. (Fig. 1) (2)Pull up the side casing(B). (Fig. 2) Fig.1 Fig.2 Fig.3...
  • Page 20 8-3 THERMISTOR (Intake air temperature detection) Be careful removing heavy parts. OPERATING PROCEDURE PHOTOS 1.Removing the thermistor Fig.1 (1)Remove the thermistor under the control box. Thermistor 8-4 DRAINPAN OPERATING PROCEDURE PHOTOS Fig.1 1.Removing the drainpan (1)Remove the fixing screw of the side frame by the control box.
  • Page 21 8-5 FAN and FAN MOTOR Be careful removing heavy parts. OPERATING PROCEDURE PHOTOS 1.Sliding the fan section (Fig.1) Fig.1 (1)Remove the fixing screws(two) (a). (2)Slide the fan section in direction of the arrow ➀. 2.Removing the fan motor (Fig.2) (1)Remove the fixing screws (two)(b) of the fan cas- ing(A).
  • Page 22 8-6 HEAT EXCHANGER Be careful removing heavy parts. OPERATING PROCEDURE PHOTOS 1.Removing the casing Fig.1 (1)Remove the fixing screws(six) and remove the casing. (Fig. 1) 2.Removing the cover1,2 with procedure 8-2 (Fig. 2) 3.Removing the Heat exchanger (1)Remove the fixing screws(four) and remove the heat exchanger support.
  • Page 23 8-7 CASING (Concealed type PFFY-NRMU) Be careful removing heavy parts. OPERATING PROCEDURE PHOTOS 1.Removing the casing ass’y Fig.1 (1)Remove the fixing screws (nine) of the plate(A) and remove the plate. (Fig. 1) 2.Removing the air diffuser ass’y (1)Remove the fixing screws (eight) of the air diffuser ass’y(B) and remove it.
  • Page 24 HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN Issued in Feb. 2014 HWE0515A New publication, effective Feb. 2014 Printed in Japan Specifications subject to change without notice...

Table of Contents