ABB RELION REX640 Operation Manual page 97

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759118 A
REX640
Operation Manual
GUID-D35FF83D-0266-4E9E-A056-E1276C32AEA1 V1 EN
Figure 88:
More information about the warning
Table 10:
Warning indications and codes
Warning indication
Watchdog reset
Power down det.
DNP3 warning
Dataset warning
Report cont. warning
GOOSE contr. warning
SCL config warning
Logic warning
SMT logic warning
GOOSE input warning
ACT warning
GOOSE rec. warning
AFL warning
SMV warning
Table continues on next page
Warning code
10
11
22
24
25
26
27
28
29
30
31
32
33
34
Section 6
Troubleshooting
Additional information
A watchdog reset has occurred.
The auxiliary supply voltage has
dropped too low.
Error in the DNP3
communication
Error in the Data set(s)
Error in the Report control
block(s)
Error in the GOOSE control
block(s)
Error in the SCL configuration
file or the file is missing
Analog channel configuration
warning
Error in the SMV configuration
91

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents