3.4. Switch-3: Setting Item Switch
There is "Setting Item Switch" which is assigned by following tables. These values are enabled when
Switch-1 is set "DISP. (SET.)" or "SETTING".
Rotary position
CBV2-A02S1
of Switch-3
U<
1
U<
2
U<
3
U>
4
U>
5
−
6
−
7
−
8
−
9
10
FREQ.
11
ALARM HOLD
−
12
13
COMM. ST. No.
−
14
15
PASSWORD
−
16
Rotary position
COC4-A02S1
of Switch-3
I>
1
I>
2
I>
3
I>>
4
I >
5
I >
6
I >
7
I >>
8
−
9
10
FREQ.
11
ALARM HOLD
−
12
13
COMM. ST. No.
−
14
15
PASSWORD
−
16
Table 3-5 Setting Item of Switch-3 (CBV2)
Description
(V)
Undervoltage operating value
TIME (s)
Undervoltage operating time
UV-TEST
Undervoltage test mode
(V)
Overvoltage operating value
TIME (s)
Overvoltage operating time
Frequency setting
Digital output condition of alarm contact by
self-diagnosis
(hold / un-hold)
Slave address of Modbus
Set password
Even though Switch-1 set "DISP. (SET.)",
current password doesn't displayed.
Table 3-6 Setting Item of Switch-3 (COC4)
Description
IDMT overcurrent operating value (51)
(A)
IDMT overcurrent time multiplier (51)
TM
IDMT characteristic curve (51)
CURVE
Instantaneous overcurrent operating value
(A)
(50)
Ground overcurrent operating value (51N)
(A)
IDMT ground overcurrent time multiplier
TM
(51N)
IDMT characteristic curve (51N)
CURVE
Instantaneous ground overcurrent
(A)
operating value (50N)
Frequency setting
Digital output condition of alarm contact by
self-diagnosis
(hold / un-hold)
Slave address of Modbus
Set password
Even though Switch-1 set "DISP. (SET.)",
current password doesn't displayed.
16 / 47
Related
chapters
Clause 4.5, 4.6
Related
chapters
Clause 4.5, 4.6
JEP0-IL9537