ABB Relion 670 Series Quick Start Manual
ABB Relion 670 Series Quick Start Manual

ABB Relion 670 Series Quick Start Manual

Version 2.2 ansi
Hide thumbs Also See for Relion 670 Series:

Advertisement

®
Relion
670/650 series
670/650 series
Version 2.2 ANSI
Quick start guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB Relion 670 Series

  • Page 1 ® Relion 670/650 series 670/650 series Version 2.2 ANSI Quick start guide...
  • Page 3 Document ID: 1MRK 500 129-UUS Issued: November 2018 Revision: B Product version: 2.2 © Copyright 2018 ABB. All rights reserved...
  • Page 5: Table Of Contents

    Table of contents Table of contents Section 1 Introduction......................3 Section 2 Safety information....................5 Symbols on the product.......................... 5 Warnings..............................5 Caution signs.............................6 Section 3 Unpacking and inspecting..................9 Removing transport packaging......................9 Inspecting the product..........................9 3.2.1 Identifying the product........................9 3.2.2 Checking delivery items........................
  • Page 6 Table of contents Section 8 Editing the network settings................35 Setting up communication between PCM600 and the IED............35 Section 9 Working with the PCM software................41 670/650 series Quick start guide...
  • Page 7: Introduction

    1MRK 500 129-UUS B Section 1 Introduction Section 1 Introduction GUID-DCFD62E5-F592-4513-84B0-EC73C7C61838 v1 The Quick Start Guide contains instructions on how to setup the Relion 670/650 series IED to get started. The guide provides instructions to setup with a preconfigured IED, however, it is also useful for the customized version of the IED.
  • Page 9: Safety Information

    1MRK 500 129-UUS B Section 2 Safety information Section 2 Safety information Symbols on the product GUID-E48F2EC3-6AB8-4ECF-A77E-F16CE45CA5FD v4 All warnings must be observed. Read the entire manual before doing installation or any maintenance work on the product. Class 1 Laser product. Take adequate measures to protect your eyes and do not view directly with optical instruments.
  • Page 10: Caution Signs

    Section 2 1MRK 500 129-UUS B Safety information M2364-2 v1 Always use suitable isolated test pins when measuring signals in open circuitry. Potentially lethal voltages and currents are present. M2370-2 v1 Never connect or disconnect a wire and/or a connector to or from a IED during normal operation.
  • Page 11 1MRK 500 129-UUS B Section 2 Safety information GUID-F2A7BD77-80FB-48F0-AAE5-BE73DE520CC2 v1 The IED contains components which are sensitive to electrostatic discharge. ESD precautions shall always be observed prior to touching components. M2695-2 v2 Always transport PCBs (modules) using certified conductive bags. M2696-2 v1 Do not connect live wires to the IED.
  • Page 13: Unpacking And Inspecting

    GUID-966A05ED-CD30-4F66-957E-00FF38943A73 v4 If damage has occurred during transport, appropriate actions must be taken against the latest carrier. Please inform the nearest ABB office or representative. Notify ABB immediately if there are any discrepancies in relation to the delivery documents. 670/650 series...
  • Page 15: Ied Hardware

    1MRK 500 129-UUS B Section 4 IED hardware Section 4 IED hardware Overview IP14270-1 v1 4.1.1 Variants of case size with local HMI display M15024-3 v6 ANSI04000458-2-en.psd ANSI04000458 V2 EN-US Figure 2: 1/2 19” case with local HMI display. 670/650 series Quick start guide...
  • Page 16 Section 4 1MRK 500 129-UUS B IED hardware ANSI05000762-2-en.psd ANSI05000762 V2 EN-US Figure 3: 3/4 19” case with local HMI display. ANSI04000460 -2-en.psd ANSI04000460 V2 EN-US Figure 4: 1/1 19” case with local HMI display. 670/650 series Quick start guide...
  • Page 17: Case From The Front And Rear Sides

    1MRK 500 129-UUS B Section 4 IED hardware 4.1.2 Case from the front and rear sides IP16286-1 v2 M16105-3 v10 Table 1: Designations for 1/2 x 19” casing with 1 TRM slot Rear position Module X31 and X32 etc. to X51 and X52 BIM, BOM, SOM, IOM or MIM X301, X302, X303, X304 X305...
  • Page 18 Section 4 1MRK 500 129-UUS B IED hardware SEMOD111882-4 v8 Table 2: Designations for 3/4 x 19” casing with 1 TRM slot Rear position Module X31 and X32 etc. to X101 and X102 BIM, BOM, SOM, IOM or MIM X301, X302, X303, X304 X305 LDCM X306...
  • Page 19 1MRK 500 129-UUS B Section 4 IED hardware SEMOD111884-4 v7 Table 3: Designations for 3/4 x 19” casing with 2 TRM slot Rear position Module X31 and X32 etc. to X71 and X72 BIM, BOM, SOM, IOM or MIM X301. X302, X303, X304 X305 LDCM X306...
  • Page 20 Section 4 1MRK 500 129-UUS B IED hardware M16106-3 v10 Table 4: Designations for 1/1 x 19” casing with 1 TRM slot Rear position Module X31 and X32 etc. to X161 BIM, BOM, SOM, IOM or and X162 X301, X302, X303, X304 X305 LDCM X306...
  • Page 21 1MRK 500 129-UUS B Section 4 IED hardware M16108-3 v10 Table 5: Designations for 1/1 x 19” casing with 2 TRM slots Rear position Module X31 and X32 etc. to X131 BIM, BOM, SOM, IOM or and X132 X301, X302, X303, X304 X305 LDCM X306...
  • Page 23: Powering Up The Ied

    1MRK 500 129-UUS B Section 5 Powering up the IED Section 5 Powering up the IED GUID-1B10552A-270B-4FFC-A065-AB30ECCE5EE0 v1 All Relion 670/650 series IEDs have either low or high power supply ranges. Low-range: 24-60 V DC High-range: 90-250 V DC How to know the voltage level GUID-ADB6E158-6051-4DF1-83B8-BE9590FF132B v1 See the label on the right-hand side of the IED to know the voltage level for the IED.
  • Page 24: How To Connect To The Power Supply

    Section 5 1MRK 500 129-UUS B Powering up the IED Transformer designations Transformer input module, rated currents and voltages Optional, customer specific information Order number, dc supply voltage and rated frequency Product type, description and serial number Product type How to connect to the power supply GUID-30AD9F73-5CA5-41A7-8283-C322AF1DA813 v2 The power supply module is on the leftmost side (rear view) of the IED.
  • Page 25: Energizing The Ied

    If the self supervision of the IED detects a diagnostic error during the start-up process, the green Normal LED flashes. Further information on the error may be visible on the local HMI under Main menu/Diagnostics/IED status/General. Note down the displayed information as reference when contacting ABB technical support. 670/650 series Quick start guide...
  • Page 27: Lhmi Overview

    1MRK 500 129-UUS B Section 6 LHMI overview Section 6 LHMI overview Local HMI AMU0600442 v15 The LHMI of the IED contains the following elements • Keypad • Display (LCD) • LED indicators • Communication port for PCM600 The LHMI is used for setting, monitoring and controlling. 6.1.1 Keypad AMU0600428 v19...
  • Page 28 Section 6 1MRK 500 129-UUS B LHMI overview ANSI15000157-1-en.vsdx ANSI15000157 V1 EN-US Figure 8: LHMI keypad with object control, navigation and command push-buttons and RJ-45 communication port 1...5 Function button Close Open Escape Left Down Right Enter Remote/Local Uplink LED Not in use Multipage Menu...
  • Page 29 1MRK 500 129-UUS B Section 6 LHMI overview Communication port Programmable indication LEDs IED status LEDs Object control If the control position of the IED is set to local with the R/L button, the controlled objects can be opened and closed using the object control buttons. Object to be controlled is selected from the single line diagram.
  • Page 30: Display

    Section 6 1MRK 500 129-UUS B LHMI overview Commands Table 8: Command push-buttons Name Description • Moving directly to Main menu, if currently in Menu any other menu or view. • Moving to the default view, if currently in Main menu. Changing the control position (remote or local) of the device.
  • Page 31 1MRK 500 129-UUS B Section 6 LHMI overview IEC15000270-1-en.vsdx IEC15000270 V1 EN-US Figure 9: Display layout Path 2 Content 3 Status 4 Scroll bar (appears when needed) • The path shows the current location in the menu structure. If the path is too long to be shown, it is truncated from the beginning, and the truncation is indicated with three dots.
  • Page 32 Section 6 1MRK 500 129-UUS B LHMI overview IEC15000138-1-en.vsdx IEC15000138 V1 EN-US Figure 10: Truncated path The function key button panel shows on request what actions are possible with the function buttons. Each function button has a LED indication that can be used as a feedback signal for the function button control action.
  • Page 33: Leds

    1MRK 500 129-UUS B Section 6 LHMI overview IEC13000240-1-en.vsd GUID-5157100F-E8C0-4FAB-B979-FD4A971475E3 V1 EN-US Figure 12: Indication LED panel The function button and indication LED panels are not visible at the same time. Each panel is shown by pressing one of the function buttons or the Multipage button. Pressing the ESC button clears the panel from the display.
  • Page 34: Local Hmi Functionality

    Section 6 1MRK 500 129-UUS B LHMI overview IEC16000076-1-en.vsd IEC16000076 V1 EN-US Figure 13: OPENCLOSE_LED connected to SXCBR 6.1.4 Local HMI functionality 6.1.4.1 Protection and alarm indication GUID-09CCB9F1-9B27-4C12-B253-FBE95EA537F5 v18 Protection indicators The protection Target LEDs are Normal, Pickup and Trip. The yellow and red status LEDs are configured in the digital fault recorder function, DRPRDRE, by connecting a pickup or trip signal from the actual function to a BxRBDR binary input function block using the PCM600 and configure the setting to...
  • Page 35 1MRK 500 129-UUS B Section 6 LHMI overview Table 12: Trip LED (red) LED state Description Disabled Normal operation. Enabled A protection function has tripped. An indication message is displayed if the auto- indication feature is enabled in the local HMI. The trip indication is latching and must be reset via communication, LHMI or binary input on the LEDGEN component.
  • Page 37: Connecting To The Pcm600 Software

    1MRK 500 129-UUS B Section 7 Connecting to the PCM600 software Section 7 Connecting to the PCM600 software GUID-DD4CDCDE-8909-48EC-96EA-93B43FA106D1 v2 The software suite used for communicating to the IED is the PCM600. This tool enables to read and modify the settings in the IED, and to view the events register, Digital fault recorder (oscillography), and other monitoring tasks.
  • Page 38: Preparing For The Connection

    PC has this functionality, then use a crossover cable. Installing the PCM600 software GUID-D0D14BE6-81C5-4D16-9D5F-2536143720CE v2 Download the latest version of PCM600 software from ABB Software Library. Follow the instructions in the installation wizard to install the software. Connecting the cables GUID-C03819DA-1243-4C59-A74F-30334C267602 v1 Connect the RJ45 Ethernet cable between the front port of the IED and the PC.
  • Page 39: Section 8 Editing The Network Settings

    1MRK 500 129-UUS B Section 8 Editing the network settings Section 8 Editing the network settings GUID-46742F3A-48A3-4C24-A354-AD721C69023C v1 Before starting the PCM600 program, edit the network settings of the computer system. The computer system and the IED should be configured to communicate correctly because both will be available on the same network.
  • Page 40 Section 8 1MRK 500 129-UUS B Editing the network settings The communication media is always Ethernet and the used transport layer is TCP/IP. Each IED has an RJ-45 Ethernet interface connector on the front. The front Ethernet connector is recommended to be used for communication with PCM600. When an Ethernet-based station protocol is used, PCM600 communication can use the same Ethernet port and IP address.
  • Page 41 1MRK 500 129-UUS B Section 8 Editing the network settings IEC13000057-1-en.vsd IEC13000057 V1 EN-US Figure 16: Select: Search programs and files Type View network connections and click on the View network connections icon. 670/650 series Quick start guide...
  • Page 42 Section 8 1MRK 500 129-UUS B Editing the network settings IEC13000058-1-en.vsd IEC13000058 V1 EN-US Figure 17: Click View network connections Right-click and select Properties. IEC13000059-1-en.vsd IEC13000059 V1 EN-US Figure 18: Right-click Local Area Connection and select Properties Select the TCP/IPv4 protocol from the list of configured components using this connection and click Properties.
  • Page 43 1MRK 500 129-UUS B Section 8 Editing the network settings IEC13000060-1-en.vsd IEC13000060 V1 EN-US Figure 19: Select the TCP/IPv4 protocol and open Properties IP address and Subnet mask if the front port is Select Use the following IP address and define IP address is not set to be obtained automatically by the IED,see used and if the Figure...
  • Page 44 Section 8 1MRK 500 129-UUS B Editing the network settings The PC and IED must belong to the same subnetwork for this set-up to work. Setting up the PC to access the IED via a network The same method is used as for connecting to the front port. The PC and IED must belong to the same subnetwork for this set-up to work.
  • Page 45: Section 9 Working With The Pcm Software

    1MRK 500 129-UUS B Section 9 Working with the PCM software Section 9 Working with the PCM software GUID-F61C3F9B-7CD0-4F92-9ACA-D4852B3FA994 v2 The Protection and Control IED Manager, PCM600, tool provides versatile functionalities for the complete life-cycle of all Relion IEDs at all voltage levels. It enables to read or write the configuration and settings from and to the IED.
  • Page 48 ABB AB Grid Automation Products SE-721 59 Västerås, Sweden Phone +46 (0) 21 32 50 00 Scan this QR code to visit our website © Copyright 2018 ABB. All rights reserved.