SUN2000-(12KTL, 15KTL, 17KTL, 20KTL)-M0
User Manual
Parameter
Control mode
Closed-loop controller
----End
Scenario 2: Multiple Inverters + SmartLogger1000A
See the
Issue 03 (2019-07-19)
SmartLogger1000A User
Copyright © Huawei Technologies Co., Ltd.
Value Range
Not restricted
Grid connected with zero
power
Power-limited grid
connected
External controller
Inverter
Manual.
C Setting Export Limitation Parameters
Description
If this parameter is set to
Not restricted, the
SUN2000 output power
is not limited. The
SUN2000 can export its
rated power to the power
grid.
If this parameter is set to
Grid connection with
zero power and the
SUN2000 is connected
to a power meter, the
output power of the
SUN2000 is supplied
only to the local load,
but not the power grid.
If this parameter is set to
Power-limited grid
connection and the
SUN2000 is connected
to a Smart power sensor,
the SUN2000 supplies
power limited based on
the setting of Grid-tied
Point Power to the
power grid.
Set this parameter to
External controller
when the
SmartLogger1000A is
connected.
If multiple inverters are
cascaded, set this
parameter to External
controller.
If a single inverter is
used, set this parameter
to Inverter.
84