Mitsubishi Electric A800 Plus Instruction Manual page 40

Separated converter type, roll to roll function
Hide thumbs Also See for A800 Plus:
Table of Contents

Advertisement

Total wiring length
Connect one or more general-purpose motors within the total wiring length 500 m. (The wiring length should be 100 m or
less under vector control.)
Total wiring length
When driving a 400 V class motor by the inverter, surge voltages attributable to the wiring constants may occur at the
motor terminals, deteriorating the insulation of the motor. In this case, take one of the following measure.
• Use a "400 V class inverter-driven insulation-enhanced motor" and set Pr.72 PWM frequency selection according to
the wiring length.
Wiring length 100 m or shorter
6 (6 kHz) or lower
• If the motor capacity is 280 kW or lower, connect the sine wave filter (MT-BSL/BSC) to the output side.
NOTE
• Especially for long-distance wiring, the inverter may be affected by a charging current caused by the stray capacitances of the
wiring, leading to a malfunction of the overcurrent protective function or fast response current limit function or a malfunction or
fault of the equipment connected on the inverter output side. If the fast-response current limit function malfunctions, disable
this function. (For the details of Pr.156 Stall prevention operation selection, refer to the FR-A800 Instruction Manual
(Detailed))
• A sine wave filter (MT-BSL/BSC) can be used under V/F control. Do not use the filters under different control methods.
• For the details of Pr.72 PWM frequency selection, refer to the FR-A800 Instruction Manual (Detailed).
• Refer to
page 84
500 m or less
Wiring length longer than 100 m
4 (4 kHz) or lower
to drive a 400 V class motor by an inverter.
Main circuit terminals
300 m
300 m
300 m + 300 m = 600 m
INSTALLATION AND WIRING
2
39