Harmonic Suppression Guidelines In Japan - Mitsubishi Electric A800 Plus Instruction Manual

Separated converter type, roll to roll function
Hide thumbs Also See for A800 Plus:
Table of Contents

Advertisement

Power supply harmonics
3.2.2

Harmonic Suppression Guidelines in Japan

Inverters have a converter section (rectifier circuit) and generate a harmonic current.
Harmonic currents flow from the inverter to a power receiving point via a power transformer. The Harmonic Suppression
Guidelines was established to protect other consumers from these outgoing harmonic currents.
The three-phase 200 V input specifications 3.7 kW or lower were previously covered by "the Harmonic Suppression
Guidelines for Household Appliances and General-purpose Products" and other models were covered by "the Harmonic
Suppression Guidelines for Consumers Who Receive High Voltage or Special High Voltage". However, the transistorized
inverter has been excluded from the target products covered by "the Harmonic Suppression Guidelines for Household
Appliances and General-purpose Products" in January 2004 and "the Harmonic Suppression Guideline for Household
Appliances and General-purpose Products" was repealed on September 6, 2004.
All capacity and all models of general-purpose inverter used by specific consumers are now covered by "the Harmonic
Suppression Guidelines for Consumers Who Receive High Voltage or Special High Voltage" (hereinafter referred to as "the
Specific Consumer Guidelines").
• "Specific Consumer Guidelines"
This guideline sets forth the maximum harmonic currents outgoing from a high-voltage or especially high-voltage receiving
consumer who will install, add or renew harmonic generating equipment. If any of the maximum values is exceeded, this
guideline requires that consumer to take certain suppression measures.
• Maximum Values of Outgoing Harmonic Currents per 1 kW Contract Power
Received power
5th
voltage
6.6 kV
3.5
22 kV
1.8
33 kV
1.2
Application of the specific consumer guidelines
• Conversion factors for FR-A800 series
Classification
Three-phase bridge
3
(Capacitor smoothing)
5
Self-excitation three-phase bridge
• Equivalent Capacity Limits
Received power voltage
6.6 kV
22/33 kV
66 kV or more
• Harmonic content (Values of the fundamental current is 100%)
reactor
Used (DC side)
∗1
Used (AC, DC sides)
∗1
∗1
The converter unit (FR-CC2) is equipped with the DC reactor on its DC side.
80
PRECAUTIONS FOR USE OF THE INVERTER
7th
11th
2.5
1.6
1.3
0.82
0.86
0.55
Install, add or renew
equipment
Calculation of equivalent
capacity total
Equal to or less
than reference
capacity
Equivalent
capacity total
Above reference
capacity
Calculation of outgoing
harmonic current
Not more than
harmonic current upper
Harmonic suppression
measures unnecessary
Circuit type
With reactor (DC side)
With reactors (AC, DC sides)
When a high power factor converter is used
Reference capacity
50 kVA
300 kVA
2000 kVA
5th
7th
30
13
8.4
28
9.1
7.2
13th
17th
1.3
1.0
0.69
0.53
0.46
0.35
More than upper limit
limit?
Harmonic suppression
measures necessary
Equal to or less
than upper limit
∗1
∗1
11th
13th
17th
5.0
4.7
4.1
3.2
19th
23rd
0.9
0.76
0.70
0.47
0.39
0.36
0.32
0.26
0.24
Conversion coefficient Ki
K33 = 1.8
K34 = 1.4
K5 = 0
19th
23rd
3.2
3.0
2.4
1.6
Over
23rd
25th
2.2
1.4