Mitsubishi Electric CITY MULTI CMH-WM-V-A Series Data Book
Mitsubishi Electric CITY MULTI CMH-WM-V-A Series Data Book

Mitsubishi Electric CITY MULTI CMH-WM-V-A Series Data Book

Air conditioning systems

Advertisement

AIR CONDITIONING SYSTEMS
MODEL
CMH-WM-V-A

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric CITY MULTI CMH-WM-V-A Series

  • Page 1 AIR CONDITIONING SYSTEMS MODEL CMH-WM-V-A...
  • Page 2: Table Of Contents

    CONTENTS Hydro unit CMH-WM-V-A I.Hydro unit 1. SPECIFICATIONS ............................ 2 2. EXTERNAL DIMENSIONS ........................5 3. CENTER OF GRAVITY ..........................7 4. ELECTRICAL WIRING DIAGRAMS ......................8 5. SOUND LEVELS ............................9 5-1. Sound levels ............................ 9 5-2. NC curves ............................9 6.
  • Page 3: Specifications

    1. SPECIFICATIONS Hydro unit I.Hydro unit 1. SPECIFICATIONS Model name CMH-WM250V-A Power source 1-phase 220-230-240 V 50 Hz 60 Hz Power input Cooling 0.74/0.74/0.74 0.74/0.74/0.74 (220/230/240) Heating 0.74/0.74/0.74 0.74/0.74/0.74 Current input Cooling 3.84/3.67/3.52 3.84/3.67/3.52 (220/230/240) Heating 3.84/3.67/3.52 3.84/3.67/3.52 Sound pressure level (measured in anechoice room) dB <A>...
  • Page 4 1. SPECIFICATIONS Hydro unit Model name CMH-WM350V-A Power source 1-phase 220-230-240 V 50 Hz 60 Hz Power input Cooling 0.90/0.90/0.90 0.90/0.90/0.90 (220/230/240) Heating 0.90/0.90/0.90 0.90/0.90/0.90 Current input Cooling 4.69/4.48/4.30 4.69/4.48/4.30 (220/230/240) Heating 4.69/4.48/4.30 4.69/4.48/4.30 Sound pressure level (measured in anechoice room) dB <A>...
  • Page 5 1. SPECIFICATIONS Hydro unit Model name CMH-WM500V-A Power source 1-phase 220-230-240 V 50 Hz 60 Hz Power input Cooling 1.06/1.06/1.06 1.06/1.06/1.06 (220/230/240) Heating 1.06/1.06/1.06 1.06/1.06/1.06 Current input Cooling 5.47/5.23/5.02 5.47/5.23/5.02 (220/230/240) Heating 5.47/5.23/5.02 5.47/5.23/5.02 Sound pressure level (measured in anechoice room) dB <A>...
  • Page 6: External Dimensions

    2. EXTERNAL DIMENSIONS Hydro unit 2. EXTERNAL DIMENSIONS CMH-WM250, 350, 500V-A Unit: mm MEES18K070...
  • Page 7 2. EXTERNAL DIMENSIONS Hydro unit CMH-WM250, 350, 500V-A Unit: mm MEES18K070...
  • Page 8: Center Of Gravity

    3. CENTER OF GRAVITY Hydro unit 3. CENTER OF GRAVITY CMH-WM250, 350, 500V-A Unit: mm Model CMH-WM250V-A CMH-WM350V-A CMH-WM500V-A MEES18K070...
  • Page 9: Electrical Wiring Diagrams

    4. ELECTRICAL WIRING DIAGRAMS Hydro unit 4. ELECTRICAL WIRING DIAGRAMS CMH-WM250, 350, 500V-A MEES18K070...
  • Page 10: Sound Levels

    5. SOUND LEVELS Hydro unit 5-1. Sound levels 5. SOUND LEVELS (Measured point) Measurement location * Measured in anechoic room. 5-2. NC curves CMH-WM250, 350, 500V-A Power Source: 220-240V (50/60Hz) NC-70 NC-60 NC-50 NC-40 NC-30 Approximate minimum audible limit on NC-20 continuous noise Octave band central frequency (Hz)
  • Page 11: Electrical Characteristics

    6. ELECTRICAL CHARACTERISTICS Hydro unit 6. ELECTRICAL CHARACTERISTICS Symbols: MCA: Max. Circuit Amps, MFA: Max. Fuse Amps, RLA: Rated Load Amps Power supply Hydro unit RLA(A) Volts Range+-10% MCA(A) MFA(A) 3.84 Max.: 264V CMH-WM250V-A 50/60 4.40 3.67 Min.: 198V 3.52 4.69 Max.: 264V CMH-WM350V-A...
  • Page 12: Installation

    7. INSTALLATION Hydro unit 7-1. Lifting method 7. INSTALLATION When hanging the unit for transportation  Use hanging holes to hang the unit.  Keep the ropes from coming into contact with the water supply and expansion vessel pipes while the unit is being hung. ≤...
  • Page 13: Optional Parts

    8. OPTIONAL PARTS Hydro unit 8-1. Drain pan 8. OPTIONAL PARTS Drain pan CMH-WM250, 350, 500V-A PAC-SH01DP-E CMH-WM-A base Hydro unit Drain pan PAC-SH01DP-E PAC-SH01DP-E Item Drain pan Additional panel Nut M10 Quantity 10 (Spare included) Shape Item Washer M10 Screw 5 ×...
  • Page 14 - Doing so may cause the unit or pipes to burst, or result in explosion or fire during use, repair, or at the time of disposal of the unit. - It may also be in violation of applicable laws. - MITSUBISHI ELECTRIC CORPORATION cannot be held responsible for malfunctions or accidents resulting from the use of the wrong type of refrigerant.