C U R R E N T A N D VO LTA G E I N S T R U M E N T T R A N S F O R M E R S
10
I N S T R U C T I O N S F O R I N S TA L L AT I O N , U S E A N D M A I N T E N A N C E
- Voltage transformers according to IEC
Variants of connections of double row terminal - One pole VT
according to IEC
1 measuring winding with no tap
1 measuring winding with 1 tap
1 measuring + residual
2 measuring winding with no tap
2 measuring winding with 1 tap
2 measuring + residual
3 measuring
2 measuring with tap + residual
with 1 tap
1 measuring with tap + residual
with 1 tap
1 measuring with tap + residual
Variants of connections of double row terminal - Double pole VT
according to IEC
1 measuring
1 measuring winding with 1 tap
2 measuring
1 measuring + residual
2 measuring winding with tap
Residual voltage windings connected to open delta must have dn terminal earthed
only on one of three transformers (earthing screws at dn terminals of others two
transformers have to be removed).