Siemens SITRANS LG260 Operating Instructions Manual page 51

Guided wave radar. four-wire modbus converter version in second chamber rod and cable probe
Hide thumbs Also See for SITRANS LG260:
Table of Contents

Advertisement

Failure (failure)
Code
Cause
Text message
F013
Sensor does not detect an echo
during operation
no measured val-
Antenna system dirty or defective
ue available
F017
Adjustment not within specification
Adjustment span
too small
F025
Index markers are not continu-
ously rising, for example illogical
Error in the line-
value pairs
arization table
F036
Failed or interrupted software
update
No operable soft-
ware
F040
Hardware defect
Error in the elec-
tronics
F041
Cable probe broken or rod probe
defective
Probe loss
F080
General software error
General software
error
F105
The instrument is still in the start
phase, the measured value could
Measured value
not yet be determined
is determined
F113
Error in the internal instrument
communication
Communication
error
F125
Temperature of the electronics in
the non-specified range
Impermissible
electronics tem-
perature
F260
Error in the calibration carried out
in the factory
Error in the cali-
Error in the EEPROM
bration
F261
Error during setup
False signal suppression faulty
Error in the in-
Error when carrying out a reset
strument settings
PBD-51041059
This status message is inactive by default. It can be activated by the
user via PACTware/DTM or EDD.
The following table shows the codes and text messages of the status
message "Failure" and provides information on causes as well as
corrective measures.
SITRANS LG260 - Operating Instructions
Rectification
Check for correct mounting and/or
parameter settings
Clean or exchange process com-
ponent or antenna
Change adjustment according
to the limit values (difference
between min. and max. ≥ 10 mm)
Check linearisation table
Delete table/Create new
Repeat software update
Check electronics version
Exchanging the electronics
Send instrument for repair
Exchanging the electronics
Send instrument for repair
Check probe and exchange, if
necessary
Briefly separate operating voltage
Wait for the end of the switch-on
phase
Duration up to approx. 3 minutes
depending on the version and
parameter settings
Briefly separate operating voltage
Send instrument for repair
Check ambient temperature
Insulate electronics
Use instrument with higher tem-
perature range
Exchanging the electronics
Send instrument for repair
Repeat setup
Repeat reset
DevSpec
Diagnosis Bits
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 13
Bit 5
Bit 6
-
Bit 7
Bit 8
Bit 9
51