Unit Code
111
112
113

10.4 Modbus RTU commands

FC3 Read Holding Register
With this command, any number (1-127) of holding registers can be read out. The start register,
from which the readout should start, and the number of registers are transmitted.
Request:
Parameter
Function Code
Start Address
Number of Registers
Response:
Parameter
Function Code
Start Address
Register Value
FC4 Read Input Register
With this command, any number (1-127) of input registers can be read out. The start register, from
which the readout should start, and the number of registers are transmitted.
Request:
Parameter
Function Code
Start Address
Number of Registers
Response:
Parameter
Function Code
Start Address
Register Value
76
Measurement Unit
Cubic Yards
Cubic Feet
Cubic Inches
Length
1 Byte
2 Bytes
2 Bytes
Length
1 Byte
2 Bytes
N*2 Bytes
Length
1 Byte
2 Bytes
N*2 Bytes
Length
1 Byte
2 Bytes
N*2 Bytes
SITRANS LG260 - Operating Instructions
Code/Data
0x03
0x0000 to 0xFFFF
1 to 127 (0x7D)
Code/Data
0x03
2*N
Data
Code/Data
0x04
0x0000 to 0xFFFF
1 to 127 (0x7D)
Code/Data
0x04
2*N
Data
PBD-51041059