20 EN – R1...R4 Quick installation guide
Connect the control cables
See figures
I
and
and one digital signal cable. Make the connections according to the default
configuration in use. The default connections of the Water default configuration are
shown in section
R1-
R4
1. Remove the front cover, if not already removed. See section
R5
and open the cover
Example of connecting an analog signal cable:
R6-
R9
2. Cut an adequate hole into the rubber grommet and slide the grommet onto the
cable. Slide the cable through a hole in the cable entry and attach the grommet to
the hole.
3. Ground the outer shield of the cable 360 degrees under the grounding clamp.
EN
Keep the cable unstripped as close to the terminals of the control board as
possible. Ground also the pair-cable shields and grounding wire at the SCR1
DE
terminal.
ES
4. Route the cable as shown in the figure.
5. Connect the conductors to the appropriate terminals of the control board and
FI
tighten to 0.5...0.6 N·m (0.4 lbf·ft).
FR
6. Tie all control cables to the provided cable tie mounts.
RU
SV
I2
on page 53. It shows an example with one analog signal cable
Default I/O connections
on page 17.
on page 21.
Switch off the power