2. Specifications
2.4. RTD module functions
Input changing rate alarm (rate alarm)
This function triggers an alarm if the temperature-converted value of a specified channel
changes by a value larger or smaller than the set alarm-change value (or change rate).
In case of Pt100:
Change rate [%] = (Present temperature-Temperature prior to alarm) ∗ 100
38
Resistance Temperature Detector 2MLF-RD4A User's Guide
Figure 16 – Process alarm function
(8500-(-2000)
Honeywell
R200
September 2010