7.3

CHECKING FLUE INTEGRITY

The integrity of the flue system and performance of the appliance can be
checked via the flue turret sample points.
Flue gas sample point
Air inlet sample point
Table 33 Key to figure 50
2
1
6720643895-67.1Wo
Fig. 50 Flue test points
▶ With the appliance case on and the appliance running at maximum.
▶ Insert the analyser probe into the air intake test point.
▶ Allow the readings to stabilise and check that:
– O
is equal to, or greater than 20.6%
2
– CO
is less than 0.2%
2
▶ If the readings are outside these limits then this indicates that there is
a problem with the flue system or combustion circuit, e.g. missing or
dislodged seals.
Fig. 51 Flue integrity test
6 720 821 670 (2018/06)
1
2
1
2
1
2
7.4

FAN PRESSURE TEST

This test is to determine if the heat cell requires
cleaning/attention.
SETTING THE APPLIANCE TO MAXIMUM
1. Remove the three screws retaining the control cover.
2. Remove the control cover.
3. Remove the plastic tool clipped inside the cover.
4. Insert the tool into the switch.
5. Using the tool set the mode switch to maximum output (MAX).
Ensure the appliance is powered up and there is a demand from the
external controls.
The power indicator will flash and the appliance will stay in this mode for
15 minutes if no further change is made to the switch.
3.
MAX
MIN
5.
Fig. 52 Setting the appliance to maximum
SERVICE AND SPARES
2.
1.
NORM
4.
6720644744-31.1Wo