Checking Flue Integrity - Bosch Worcester Greenstar 8000 Series Installation And Maintenance Instructions Manual

Gas fired condensing system boiler
Table of Contents

Advertisement

Commissioning
START
Set boiler to
HERE
maximum rate.
<
= less than
= greater than
or equal to
No
Record values.
Do not adjust
the gas valve.
Turn off boiler and
call Worcester, Bosch
Group help line.
0330 123 3366
Fig. 67 Commissioning checks flow chart
6.10

Checking flue integrity

Flue integrity check
▶ The combustion casing must be fitted whilst this test is carried out.
▶ Refit the test point plugs after the test has been completed.
The integrity of the flue system and performance of the appliance can be
checked via the flue turret/adaptor sample points.
Air inlet sample point location on flue turret/adaptor.
44
Zero the analyser
in fresh air.
See notice above
O
≥ 20.6%
2
No
CO
< 0.2%
2
Yes
CO < 350ppm
CO/CO
ratio
2
< 0.004
Check CO and combustion
Yes
No
Flue integrity test
using analyser
Verify flue integrity
Check all seals around the
burner, internal flue seals,
and case seals.
Rectify where necessary.
ratio at minimum rate
CO < 350ppm
CO/CO
ratio
2
< 0.004
Fig. 68 Flue integrity check test point
[1]
Air inlet sample point
[2]
Flue turret air inlet blank plug (with retaining ring)
[3]
Flue adaptor air inlet blank plug
▶ With the appliance casing on and the appliance running at maximum
output in chimney sweep mode, remove the blanking plug [2 or 3] for
the air inlet sample point [1].
▶ Insert the analyser probe into the air inlet sample point [1].
▶ Allow the readings to stabilise and check that:
– O
is equal to, or greater than 20.6%
2
– CO
is less than 0.2%
2
▶ If the readings are outside these limits then this indicates that there
is a problem with the flue system or combustion circuit.
O
≥ 20.6%
2
Yes
CO
< 0.2%
2
No
Check CO and
combustion ratio
at maximum rate
CO < 350ppm
No
CO/CO
< 0.004
Yes
Set boiler to
minimum rate.
Boiler is operating
satisfactorily.
Yes
No further action
is required.
1
2
3
0010015568-001
Greenstar 8000 Style – 6720883855 (2019/01)
ratio
2
0010023581-002

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Worcester gr8700iw 30 s ngWorcester gr8700iw 35 sb ngWorcester gr8700iw 30 s lpgWorcester gr8700iw 35 s lpgWorcester gr8700iw 30 sb lpgWorcester gr8700iw 35 sb lpg ... Show all

Table of Contents