Fault
Irregular running
Vibrations
Running noises
Motor overheats
(surface temperature
> 140 °C (284 °F))
Temperature monitoring
responds
8

Inspection, maintenance, disposal

Clean according to the degree of local contamination in order to ensure that the waste heat
is adequately dissipated.
As the operating conditions vary greatly, one can only cite general intervals for fault-free
operation.
Guidelines:
-
Bearing service life 20,000 hours
-
Radial shaft seals approx. 5,000 hours with oil lubrication.
The encoder system must be readjusted each time after the motor has been
disassembled.
Dispose of the motor in accordance with the national and local regulations in the standard
recycling process or return it to the manufacturer.
Dispose of the encoder electronics properly as electronic scrap.
20
ENGLISH
Cause
Inadequate screening of the
motor or encoder cable.
Amplification of the drive control-
ler too high
Coupling elements or driven
machine are badly balanced
Inadequate alignment of the drive
train
Fixing screws are loose
Foreign bodies inside the motor
Bearing damage
Drive overloaded
Heat dissipation impaired by
deposits
NOTICE
610.40 700.21
Remedy
Check screening and grounding (see
Section 5.1)
Adjust controller (see converter operat-
ing manual)
Rebalance
Realign the machine set
Check and tighten screw connections
Repair by the manufacturer
Repair by the manufacturer
Check load (see type plate)
Clean surface of drives.
Ensure that the cooling air can flow
freely in and out