[7-7 Error Code Definitions and Solutions: Codes [5000 - 5999] ]
7-7-3

Error Code [5110]

1. Error code definition
Heatsink temperature sensor (THHS) fault (Detail code 01)
2. Error definition and error detection method
When a short or an open of THHS is detected just before or during the inverter operation.
3. Cause, check method and remedy
Cause
(1)
INV board failure
For inverter-related error codes, refer to the following page(s). [8-9 Troubleshooting Inverter Problems]
7-7-4

Error Code [5201]

1. Error code definition
High-pressure sensor fault (63HS1)
2. Error definition and error detection method
If the high pressure sensor detects 0.098MPa [14psi] or less during the operation, the outdoor unit stops once, turns to anti-
restart mode for 3 minutes, and restarts after 3 minutes when the detected high pressure sensor is 0.098MPa [14psi] or more.
If the high pressure sensor detects 0.098MPa [14psi] or less just before the restart, the outdoor unit makes an error stop, and
the error code "5201" will appear.
During 3-minute antirestart mode, preliminary errors will be displayed on the LED display.
A error is not detected for 3 minutes after the compressor start, during defrost operation, or 3 minutes after defrost operation.
3. Cause, check method and remedy
(1)
High pressure sensor failure
(2)
Pressure drop due to refrigerant leak
(3)
Torn wire coating
(4)
A pin on the male connector is missing or contact failure
(5)
Disconnected wire
(6)
High pressure sensor input circuit failure on the control board
40
- chapter 7
If the problem recurs when the unit is put into operation, replace the INV board.
Cause
Check method and remedy
Check method and remedy
Refer to the following page(s). [8-5-1 Com-
paring the High-Pressure Sensor Measure-
ment and Gauge Pressure]
HWE18240_GB