System Configurations - Mitsubishi Electric PUHY-HP72 Service Handbook

Table of Contents

Advertisement

[2-1 System Configurations ]

2 Restrictions
2-1

System Configurations

1. Table of compatible indoor units
The table below summarizes the types of indoor units that are compatible with different types of outdoor units.
(1) Standard series
Outdoor units
HP72
T(Y)NU-A
HP96
T(Y)NU-A
HP120
T(Y)NU-A
HP144
T(Y)SNU-A
HP192
T(Y)SNU-A
HP240
T(Y)SNU-A
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
HWE18240_GB
Composing units
-
-
-
-
-
-
-
-
-
HP72
HP72
-
HP96
HP96
-
HP120
HP120
-
Maximum total
Maximum
capacity of con-
number of
nectable indoor
connect-
units
able indoor
units
36 - 93
15
48 - 124
20
60 - 156
28
72 - 187
31
96 - 249
41
120 - 312
50
Types of connectable
indoor units
P05 - P96 models
R410A series indoor units
chapter 2 -
1