8.
Reference fig. 7 and 8 - Installing switch.
Note: The HCP switch ships as a branch device with
lugs located on the load end of the switch.
To make switch a Main device, remove lugs from
load side and install lugs on line side of switch and
torque bolts to the values specified on the switch.
Position the switch so that the load side connectors are above
and below the stab and the holes are aligned. Using the 5/16-18
hex head bolts (item 9), the 5/16" lock washers (item 16) and the
5/16" flat washers (item 10) attach the switch to the connectors
using the inserts (item 24). Do not tighten. Repeat steps for all
phases. Attach switch to support (item 12) using the two 1/4-20 X
1" machine screws (item 2) through the line side of the switch and
into the support. Tighten screws. Tighten and torque the 5/16-18
bolts (item 9) to values shown on rear of deadfront.
9
10
SWITCH
STAB
24
Figure 7
2
12
Figure 8
9.
Reference fig. 9 - Installing ground assembly.
Orient the ring terminal on one end of the ground
assembly (item 11) over the 0.171" hole in the switch
main bracket (item 14). Orient the other ring terminal
on the ground assembly over the 0.171" hole in the
switch. Insert one 10-32 X 1/4" screw (item 4)
through the ring terminal and into the 0.171" hole in
the switch main bracket and tighten. Insert one
10-32 X 1/4" screw through the ring terminal and
into the 0.171" hole in the switch and tighten.
16
Figure 9
10.
Re-install the deadfront and gutter covers.
SMSKHCP for Main Mounting
Type SENTRON HCP SWITCH
14
4
11
This device/system may only be set up and used in conjunction with these instructions. Installation, mainte-
nance and operation of this device/system may only be performed by qualified personnel.
context of these instructions, qualified persons are defined as persons who have the skills and knowledge
related to the construction and operation of the electrical equipment and installations and have received
safety training to recognize and avoid the hazards involved.
qualified personnel. Within the
11-D-1023-01 REV. 0

Advertisement

loading

Summary of Contents for Siemens P5

  • Page 1 Reference fig. 7 and 8 - Installing switch. Reference fig. 9 - Installing ground assembly. Note: The HCP switch ships as a branch device with Orient the ring terminal on one end of the ground lugs located on the load end of the switch. assembly (item 11) over the 0.171”...
  • Page 2: Installation Instructions

    The following instructions are for the installation of Siemens Sentron HCP switches in 0.312” diameter hole in the long phase connector outer (item 19) a deep type panelboard (P5) as a Main. The parts provided in this kit are for into the section bus. Hand tighten. Repeat for remaining three connection to a 3 phase / 4 wire system.

This manual is also suitable for:

Smskhcp