en | Installing
The following conditions apply for an RS-485 bus system:
To use RS-485 mode at the AMC2-4R4 , connect the data cables
to the pluggable screw connector of the RS-485 host interface.
The setting of the AMC2-4R4 must correspond with the settings
of the RS-232 / RS-485 converter.
Figure 4.11: RS-485 host interface
2013-08 | AMC2-4R4 |
A bus system consists of a bus line and/or one or more
branch lines.
Cable lengths exceeding 100 m (300 ft) must be installed
as bus lines.
Branch lines are branching connections from a bus line.
Peripheral devices are AMC2 which are connected to the
host computer.
Maximum cable length of a bus line must not exceed
1200 m (4000ft).
The cable length of branch lines must not exceed 100m
(330ft).
Any bus line conductor connects up to eight AMC2. Do not
exceed the maximum number of devices.