7.7.4 1:1 Communication (Computer Link (Ethernet))
Overview
A 1:1 computer link connects the FP-X and a computer using a UTP cable (CAT5). Communication is
conducted via commands from the computer and responses from the PLC.
1:1 Communication setting (Computer link (Ethernet))
This setting enables the 1:1 communication between the FP-X and a computer using the computer link
(Ethernet).
System register setting of FP-X (specified using FPWIN GR)
Dialog box of PLC system register setting
COM1 port setting (AFPX-COM5)
No.
Setting item
No.410
Unit number
No.412
Communication mode
No.413
Communication format
No.415
Baud rate
10
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Setting value
1
Computer link
Char. bit
8 bits
Parity check
Odd
Stop bit
1 bit
Terminator
CR
Header
STX not exist
9600 bps