7.2 Communication Specifications
Communication port (Ethernet)
Interface
Number of connections
Communication mode
Target item
■Communication specifications Interface: Ethernet
Item
Interface
Transmission
Baud rate
specifications
Transmission method
Max. segment length
Communication cable
Protocol
Function
Note1) The length between a HUB and the module.
7.7 Ethernet Communication (AFPX-COM5)
Described on the next page.
13.2 Troubleshooting
13.2.11 A Communication Error has Occurred through Ethernet
■Condition: No communication with Ethernet port of AFPX-COM5
●Procedure 1
Check if the LAN cable is securely connected to each unit or a PC.
When using a HUB for the connection, check if the power supply of the HUB is on.
●Procedure 2
Check if the LINK/ACT LED of the COM5 cassette lights up.
- When the LED is off, the LAN cable is not connected correctly.
●Procedure 3
Check the IP addresses of the COM5 cassette and the destination.
●Procedure 4
Check if the communication format and baud rate for the COM1 port of the FP-X matches the configuration
setting of the AFPX-COM5.
16.1 Dimensions - When Installing Add-on Cassette
Note) The AFPX-COM5 is 5 mm taller than other communication cassettes.
4
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Computer link
IEEE802. 3u, 10BASE-T/100BASE-TX
Max. 3 connections
Server
AFPX-COM5
IEEE802. 3u, 10BASE-T/100BASE-TX
Connector shape: RJ45
100 Mpbs/10 Mbps
Baseband
100 m
UTP (Category 5)
TCP/IP, UDP/IP, ICMP, ARP
Auto-negotiation function
MDI/MDI-X Auto-crossover function
General-purpose serial communication
Max. 1 connection
Client, Server
Specifications