Download Print this page
ABB COV-6 Instruction
Hide thumbs Also See for COV-6:

Advertisement

Quick Links

Effective:
September 1995
Supersedes I.L. 41-116.1 dated May 1981
( | ) Denotes Change Since Previous Issue
!
CAUTION
Before putting relays into service, remove all
blocking which may have been inserted for the
purpose of securing the parts during shipment,
make sure that all moving parts operate freely,
inspect the contacts to see that they are clean
and close properly, and operate the relay to check
the settings and electrical connections.
1. APPLICATION
These relays have been specially designed and
tested to establish their suitability for Class 1E appli-
cations. Materials have been selected and tested to
insure that the relays will perform their intended func-
tion for their design life when operated in a normal
environment as defined by ANSI standard C37.90-
1989, when exposed to radiation levels up to 10
rads, and when subjected to seismic events produc-
ing a Shock Response Spectrum within the limits of
the relay rating.
"Class 1E" is the safety classification of the electric
equipment and systems in nuclear power generating
stations that are essential to emergency shutdown of
the reactor, containment isolation, cooling of the reac-
tor, and heat removal from the containment and reac-
tor, or otherwise are essential in preventing significant
release of radioactive material to the environment.
The type COV relay is applicable where it is desired
that an overcurrent unit be set to operate on less than
full load current when the voltage falls below a prede-
termined value, and it is desired not to operate for any
All possible contingencies which may arise during installation, operation or maintenance, and all details and
variations of this equipment do not purport to be covered by these instructions. If further information is desired
by purchaser regarding this particular installation, operation or maintenance of this equipment, the local ABB
Power T&D Company Inc. representative should be contacted.
Printed in U.S.A.
ABB Power T&D Company Inc.
Relay Division
Coral Springs, FL 33065
Type COV
Voltage Controlled Overcurrent
Relay for Class 1E Applications
magnitude of current when the voltage is above the
predetermined value. A typical application is overcur-
rent back-up protection for generators.
This instruction leaflet applies to the following types
of relays:
Type COV-6
Type COV-7
Type COV-8
Type COV-9
Type COV-11
2. CONSTRUCTION AND OPERATION
The relay consists of an overcurrent unit, a voltage
unit with adjustable resistor, an indicating contactor
switch unit, an indicating instantaneous trip unit when
required and a slow-release telephone type relay, "T"
(see Figure 1).
4
2.1. OVERCURRENT UNIT (CO)
The electromagnets for the types COV-6, COV-7,
COV-8 and COV-9 relays have a main tapped coil
located on the center leg of an "E" type laminated
structure that produces a flux which divides and
returns through the outer legs. A shading coil causes
the flux through the left leg to lag the main pole flux.
The out-of-phase fluxes thus produced in the air gap
cause a contact closing torque.
The electromagnet for the type COV-11 relay has a
main coil consisting of a tapped primary winding. Two
identical coils on the outer legs of the lamination
structure are connected to the main coil secondary in
combination of all the fluxes produced by the electro-
Instruction Leaflet
41-116.1A
Definite Minimum Time Relay
Moderately Inverse Time Relay
Inverse Time Relay
Very Inverse Time Relay
Extremely Inverse Time Relay

Advertisement

loading

Summary of Contents for ABB COV-6

  • Page 1 If further information is desired by purchaser regarding this particular installation, operation or maintenance of this equipment, the local ABB Power T&D Company Inc. representative should be contacted.
  • Page 2 41-116.1A magnet result in out-of-phase fluxes in the air gap. secured to the frame by a locking nut. The bearing The out-of-phase air gap fluxes produced cause a can be replaced if necessary, without having to contact closing torque. remove the magnetic core from the frame. The electromagnet has two pairs of voltage coils.
  • Page 3 41-116.1A torque from being produced in the overcurrent unit. 3.4.1. Trip Circuit Constants This arrangement yields a tripping characteristic as Indicating Contactor Switch Coil. shown in Figure 3. Ampere Pickup Ohms dc Resistance 3.1. OVERCURRENT UNIT 0.37 The relays are generally available in the following 0.10 overcurrent unit ranges: RANGE...
  • Page 4: Adjustments And Maintenance

    41-116.1A reclosing will be initiated immediately after a trip by relay panel. Ground wires should be affixed to the the CO contact, the time of the opening of the con- mounting screws as required for poorly grounded or tacts should be a minimum. This condition is insulated panels.
  • Page 5 41-116.1A contacts until they deflect the stationary con- stop at tap value current minus 3%. tact to a position where the stationary contact C. Time Curve – Table 1 shows the time curves cal- is resting against its backstop. The index ibration points for the various types of relays.
  • Page 6: Routine Maintenance

    41-116.1A 6.1.4. Voltage Unit (V) removed first. The screw connection holding the lead to the moving contact 1. Contact Gap – The gap between the stationary should be removed next. The second contact and moving contact with the relay in a de- screw holding the moving contact assem- energized position should be approximately .020”.
  • Page 7 41-116.1A With the time dial set on “O”, wind up the spiral ing the left-hand plug, front view, increases the spring by means of the spring adjuster until operating time and withdrawing the right-hand approximately 6-3/4 convolutions show. plug, front view, decreases the time.) In adjusting the plugs, one plug should be screwed in com- The spiral spring can be adjusted with the spring pletely and the other plug run in or out until the...
  • Page 8: Renewal Parts

    41-116.1A a) Contact Wipe – Adjust the stationary contacts screw in the stationary contact until both con- so that both stationary contacts make with the tacts just close as indicated by a neon lamp in moving contacts simultaneously and wipe 1/4” the contact circuit.
  • Page 9 Burden Drop-out Frequency Volts Continuous At 120 Volts Ratio 80-100 + Volt-Ampere burden is average for the various settings. COV-6 OVERCURRENT UNITS Volt Amperes * * Continuous One Second Power At 3 Times At 10 Times At 20 Times Ampere...
  • Page 10: Energy Requirements

    41-116.1A ENERGY REQUIREMENTS COV-7 OVERCURRENTS UNITS Volt Amperes * * Continuous One Second Power At 3 Times At 10 Times At 20 Times Ampere Rating Rating * Factor Tap Value Tap Value Tap Value Tap Value Range (Amperes) (Amperes) Angle Ø Current Current Current...
  • Page 11 41-116.1A ENERGY REQUIREMENTS COV-8 INVERSE TIME AND COV-9 VERY INVERSE TIME RELAYS VOLT AMPERES * * Continuous One Second Power At 3 Times At 10 Times At 20 Times Ampere Rating Rating * Factor Tap Value Tap Value Tap Value Tap Value Range (Amperes)
  • Page 21 41-116.1A Sub 4 3519A66 Figure 11. Outline and Drilling Plan for the Type COV Relay in Type FT21 Case...

This manual is also suitable for:

Cov-7Cov-9Cov-11Cov-8