Rack-Mounted Device - Siemens SIPROCESS GA700 Compact Operating Instructions

Continuous gas analysis, devices in explosion-proof design
Hide thumbs Also See for SIPROCESS GA700:
Table of Contents

Advertisement

Available languages

Available languages

Connecting/disconnecting of signal cables (new)
For devices in type of protection "non sparking": The device must be de-energized before
connect/disconnect signal cable plugs.
Note
Securing connectors (new)
Secure connectors without interlock mechanically, for example, with a cable tie. For more
information on securing connectors, see:
● Rack-mounted device:
→ Connection of the signal cables (Page 43)
→ Connecting the power supply (Page 42)
● Wall-mounted device: → Connecting the power supply (Page 45)
4.2.2

Rack-mounted device

Protection for use in Zone 2
Equip the device including electrical connections and front plate with suitable protection for
use in Zone 2 which meets the required IP degree of protection and the mechanical degree
of protection.
Failure to adhere to these guidelines can result in injury and/or property and environmental
damages.
Equipotential bonding
Connect the device to the equipotential bonding.
A threaded bolt M4 is available on the rear of the device to connect the equipotential bonding.
Then connect a ring cable lug with spring washer to the threaded bolt.
Failure to adhere to these guidelines can result in injury and/or property and environmental
damages.
Devices in explosion-proof design
Compact Operating Instructions, 05/2015, A5E35134047-02
CAUTION
CAUTION
CAUTION
Connecting
4.2 Electrical connections
41

Advertisement

Chapters

Table of Contents
loading

Table of Contents