Download Print this page

ABB ACS880 Manual

Master follower d2d tips and hints
Hide thumbs Also See for ACS880:

Advertisement

Quick Links

ACS880 M
AND HINTS
Overview:
This document will give recommendations for commissioning an ACS880 Master Follower setup using
the embedded D2D connection.
Description:
Master-follower D2D depends on several key points:
A physical (wired) connection must exist between the drives.
Each drive must have a unique address on the D2D (drive-to-drive) network (60.02).
The master should be transmitting a CW (command word), a speed and torque reference.
The follower receives and uses the master CW for start/stop and the master speed & torque references.
The drives must be placed in master and follower modes, respectively.
Optionally, additional data may also be passed between the master and follower (see firmware manual).
It is highly advised to use Composer Pro software for commissioning...in this example both drives (one
master and one follower) will be connected together using Panel port to provide a single programming
connection point for both drives.
NOTES
1. Each drive should have an individual, successful startup as a stand-alone drive, tested to run (typically
from the Control Panel) including an ID Run; the assumption here is that both drives start with a
parameter set that has default values.
2. Panel Bus Configuration
Using the master Control Panel, verify 49.01 (Panel port node ID number) is 1.
Using the master Control Panel, select Menu>Settings>Edit Texts to 'label' the drive.
Using the follower Control Panel, set 49.01 to 2; this gives it a unique address.
Using the follower Control Panel, select Menu>Settings>Edit Texts to 'label' the drive.
Author: Louis Chatfield, Industrial Application
Engineering
Internal (abbnow) or
External
http://www.abb.us/drives. Industry – Industrial
Product Categories: ACS880
F
ASTER
OLLOWER
D2D
Date: December 19, 2018
Document #: LVD-EOTN133U-EN
Revision: A
TIPS

Advertisement

loading

Summary of Contents for ABB ACS880

  • Page 1 ASTER OLLOWER TIPS AND HINTS Overview: This document will give recommendations for commissioning an ACS880 Master Follower setup using the embedded D2D connection. Description: Master-follower D2D depends on several key points: A physical (wired) connection must exist between the drives.
  • Page 2 Laptop with Composer Pro will connect via USB to the Control Panel attached to the master. 3. Connect the D2D (white) connectors with shielded, twisted-pair cable (3-wire, straight thru). 4. Use the ACS880 parameters shown in the 800/880 master-follower guide: Typically the master is a speed-controlled drive; the follower can be speed or torque.
  • Page 3 10. Remove the Control Panel cradle Ethernet cables, reinstall the Control Panels and save the drive files to their individual Control Panels. Using the parameters shown in the ACS800/ACS880 Master Follower Guide, if a fault occurs on the follower it will be shown on the master; this is because the follower SW (status word) is transmitted back to the master.
  • Page 4 Author: Louis Chatfield, Industrial Application Engineering Date: December 19, 2018 Internal (abbnow) or Document #: LVD-EOTN133U-EN External http://www.abb.us/drives. Industry – Industrial Revision: A Product Categories: ACS880...